beautypg.com

Sound power rating, Capacity ratings - (ari 360), Gas heat ratiings – York DM 300 User Manual

Page 9

background image

262259-YTG-E-1008

Johnson Controls Unitary Products

9

NOTE: All gas units are two-stage heating.
First stage is 50% of total.
S.S.E. = Steady State Efficiency (80%) - output divided by input.

TABLE 1: SOUND POWER RATING

1

UNIT

SIZE

CFM

ESP

BLOWER

SOUND POWER (db 10

-12

Watts)

Octave Band Centerline Frequency (Hz)

SWL

dB(A)

dB(A)

@

10Ft.

2

IWG

RPM

BHP

63

125

250

500

1,000

2,000

4,000

8,000

180

6,000

1.00

1,080

4.60

99

99

89

82

84

77

72

67

89

56

240

8,000

1.00

1,120

6.65

102

102

92

85

87

80

75

70

92

59

300

10,000

1.30

1160

12.5

108

108

98

91

93

86

81

76

98

65

1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The

dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee
requiring a dBA value or sound data in any other form than sound power level ratings.

2. At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATINGS - (ARI 360)

1

1. Certified in accordance with the Unitary Large Equip-

ment certification program which is based on ARI Stan-
dard 340/360.

MODEL

MBH

EER

2

2. EER = Energy Efficiency Ratio at full load - the cooling

capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).

IPLV

3

3. IPLV = Integrated Part Load Value.

COOLING ONLY

DM180C00

176

8.7

9.2

DM240C00

234

8.6

8.05

DM300C00

272

8.5

9.2

COOLING WITH GAS HEAT

DM180N/S

176

8.5

9.0

DM240N/S

232

8.5

8.05

DM300N/S

272

8.5

9.0

COOLING WITH ELECTRIC HEAT

DM180E18

176

8.7

9.2

DM180E36

176

8.6

9.1

DM180E54

174

8.5

8.7

DM180E72

174

8.5

8.7

DM240E18

234

8.5

8.05

DM240E36

234

8.5

8.05

DM240E54

232

8.5

8.05

DM240E72

232

8.5

8.05

DM300E18

272

8.5

9.1

DM300E36

272

8.5

9.1

DM300E54

270

8.5

9.0

DM300E72

270

8.5

9.0

TABLE 3: GAS HEAT RATIINGS

MODEL

MBH INPUT

MBH OUTPUT

DM180N/S24

300

240

DM180N/S32

400

320

DM240N/S24

300

240

DM240N/S32

400

320

DM300N/S24

300

240

DM300N/S32

400

320

For units with VFD and electric or gas heat, the speed of
the indoor blower motor continues to be controlled by
duct static pressure via the VAV control board.

If there are VAV boxes present in the duct system, the
boxes must be driven to the full-open position using a
customer-supplied power source to assure adequate
airflow across electric heating elements or gas heat
exchanger tubes.