York DM 300 User Manual

Page 15

background image

262259-YTG-E-1008

Johnson Controls Unitary Products

15

TABLE 6: DM 300 COOLING CAPACITIES (25 TON) (CONTINUED)

AIR ON

EVAPORATOR

COIL

TEMPERATURE OF AIR ON CONDENSER COIL

115°F

TOTAL

CAP.

1

MBH

POWER

INPUT

2

KW

SENSIBLE CAPACITY, MBH

ENTERING DRY BULB, °F

CFM

WB

°F

90

85

80

75

70

65

7500

77

298.7

36.0

144.7

109.0

73.4

-

-

-

72

277.7

35.4

199.3

163.7

128.1

92.4

-

-

67

256.6

34.8

254.0

218.4

182.7

147.1

111.5

-

62

236.9

34.0

236.9

236.6

201.0

165.4

129.7

94.1

57

234.7

34.5

234.7

234.7

202.9

167.2

131.6

96.0

8750

77

302.4

36.1

183.4

120.5

78.3

-

-

-

72

281.1

35.5

221.0

178.8

136.7

94.6

-

-

67

259.8

34.9

258.5

237.2

195.1

153.0

110.9

-

62

239.9

34.1

239.9

239.7

214.6

172.5

130.4

88.2

57

237.6

34.6

237.6

237.6

216.6

174.5

132.4

90.3

10000

77

306.1

36.3

222.2

131.9

83.3

-

-

-

72

284.5

35.7

242.6

194.0

145.4

96.8

-

-

67

263.0

35.1

263.0

256.1

207.5

158.9

110.3

-

62

242.8

34.2

242.8

242.8

228.2

179.6

131.0

82.4

57

240.5

34.8

240.5

240.5

230.4

181.8

133.2

84.6

11250

72

287.9

35.9

258.4

203.1

147.7

92.4

-

-

67

266.1

35.3

266.1

262.7

210.8

155.4

100.1

-

62

245.7

34.5

245.7

245.7

231.8

176.5

121.1

65.8

57

243.3

35.0

243.3

243.3

234.0

178.7

123.3

68.0

12500

72

291.3

36.1

274.2

212.1

150.0

87.9

-

-

67

269.3

35.5

269.3

269.3

214.1

152.0

89.9

-

62

248.6

34.7

248.6

248.6

235.5

173.4

111.3

49.2

57

246.2

35.2

246.2

246.2

237.7

175.6

113.5

51.4

1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor-

mance Table for the KW of the supply air blower motor.

2. These ratings include the condenser fan motors (Total 2.1 KW) and the compressor motors but not the supply air blower motor.