York DM 300 User Manual

Page 11

background image

262259-YTG-E-1008

Johnson Controls Unitary Products

11

TABLE 4: DM 180 COOLING CAPACITIES (15 TON) (CONTINUED)

AIR ON

EVAPORATOR

COIL

TEMPERATURE OF AIR ON CONDENSER COIL

115°F

TOTAL

CAP.

1

MBH

POWER

INPUT

2

KW

SENSIBLE CAPACITY, MBH

ENTERING DRY BULB, °F

CFM

WB

°F

90

85

80

75

70

65

4500

77

176.8

20.4

98.3

77.0

55.6

-

-

-

72

161.9

19.5

124.1

102.7

81.3

59.9

-

-

67

147.0

18.6

147.0

128.4

107.0

85.6

64.2

-

62

135.8

18.1

135.8

135.8

121.1

99.7

78.3

56.9

57

135.8

18.2

135.8

135.8

121.1

99.7

78.3

56.9

5250

77

183.4

20.5

126.5

86.6

61.3

-

-

-

72

167.9

19.6

140.2

114.9

89.6

64.4

-

-

67

152.5

18.8

152.5

143.2

118.0

92.7

67.5

-

62

140.9

18.3

140.9

140.9

133.6

108.3

83.0

57.7

57

140.9

18.4

140.9

140.9

133.6

108.3

83.0

57.7

6000

77

190.0

20.7

154.6

96.3

67.0

-

-

-

72

174.0

19.8

156.3

127.2

98.0

68.8

-

-

67

158.0

18.9

158.0

158.0

129.0

99.8

70.7

-

62

146.0

18.4

146.0

146.0

146.0

116.8

87.7

58.5

57

146.0

18.5

146.0

146.0

146.0

116.8

87.7

58.5

6750

72

178.4

20.1

169.6

140.7

107.5

74.3

-

-

67

162.0

19.2

162.0

162.0

141.5

108.3

75.1

-

62

149.7

18.6

149.7

149.7

149.7

116.5

83.3

50.1

57

149.7

18.7

149.7

149.7

149.7

116.5

83.3

50.1

7500

72

182.8

20.3

182.8

154.3

117.0

79.7

-

-

67

166.0

19.4

166.0

166.0

154.0

116.7

79.5

-

62

153.4

18.9

153.4

153.4

153.4

116.1

78.9

41.6

57

153.4

19.0

153.4

153.4

153.4

116.1

78.9

41.6

1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor-

mance Table for the KW of the supply air blower motor.

2. These ratings include the condenser fan motors (Total 1.5 KW) and the compressor motors but not the supply air blower motor.

Nominal Rating