Equalization Charging
975-0004-01-02 Rev D
79
Equalization Setpoints (Non-Sealed Batteries Only)
Table B-1 Typical Bulk and Float Setpoints for Batteries
Battery Type
Bulk Volts
Float Volts
Equalizing
Charge
Default Settings (knobs
at nine o’clock position)
14.0 Vdc
13.5 Vdc
Disabled
(manual
jumper)
Sealed Gel Lead Acid
Battery
14.1 Vdc
13.6 Vdc
Non
recommended.
Consult Battery
manufacturer.
AGM Lead Acid
Battery
14.4 Vdc
13.4 Vdc
Charge to
15.5 Vdc or per
manufacturer.
Maintenance-Free
RV/Marine
14.4 Vdc
13.4 Vdc
Limited
appropriateness
- if water level
can be checked.
Deep-Cycle, Liquid
Electrolyte Lead
Antimony Battery
14.6 Vdc
13.4 Vdc
Charge to
15.5 Vdc or per
battery
manufacturer.
NiCad or NiFe Alkaline
Battery
a
a.For NiCad and NiFe batteries, you must clip the R46 resistor and add 2 volts to the values
for BULK AND FLOAT shown on the circuit board. For example, set the BULK for
16.0 V adjust the BULK knob to 14.0 V after clipping R46. Values above are for batteries
at room temperature. For applications with significant temperature variations or systems
with sealed batteries, install a battery temperature sensor.
16.0 Vdc
14.5 Vdc
Not
recommended.
Consult battery
manufacturer.
Values shown are for 12-volt systems. For 24-volt Systems, multiply this
setting shown by 2. For 48-volt systems, multiply the settings shown by 4.
Important: The following settings (Table B-1) are guidelines only. Refer to
your battery vendor for specific settings and battery maintenance guidelines.