Xantrex Technology C40 User Manual
Page 45
Adjusting the C-Series Voltage Settings
975-0004-01-02 Rev D
25
The scale for the Low Voltage Disconnect setting is
calibrated as follows:
•
12-volt system: 10.5 to 12.5 volts
in increments of 0.2 volts,
•
24-volt system: 21.0 to 25.0 volts
in increments of 0.4 volts, and
•
48-volt system: 42.0 to 50.0 volts
in increments of 0.8 volts.
Figure 2-12 LVR and LVD Settings for Load Control Mode
12-Volt System Settings
24-Volt System Settings
14.0
12.0
13.0
L
.
V
.
R
(LOAD)
L
OW
V
OLTAGE
R
ECONNECT
12.2
12.4
12.6
12.8
13.2
13.4
13.6 13.8
12.5
10.5
11.5
10.7
10.9
11.1
11.3
11.7
11.9
12.1 12.3
L
.
V
.
D
(LOAD)
L
OW
V
OLTAGE
D
ISCONNECT
28.0
24.0
26.0
24.4
24.8
25.2
25.6
26.4
26.8
27.2 27.6
25.0
21.0
23.0
21.4
21.8
22.2
22.6
23.4
23.8
24.2 24.6
L
.
V
.
R
(LOAD)
L
OW
V
OLTAGE
R
ECONNECT
L
.
V
.
D
(LOAD)
L
OW
V
OLTAGE
D
ISCONNECT
56.0
48.0
52.0
48.8
49.6
50.4
51.2
52.8
53.6
54.4 55.2
50.0
42.0
46.0
42.8
43.6
44.4
45.2
46.8
47.6
48.4 49.2
L
.
V
.
R
(LOAD)
L
OW
V
OLTAGE
R
ECONNECT
L
.
V
.
D
(LOAD)
L
OW
V
OLTAGE
D
ISCONNECT
48-Volt System Settings (C40 only)