Pv charge control mode wiring, Warning: shock hazard – Xantrex Technology C40 User Manual
Page 64
Installation
44
975-0004-01-02 Rev D
PV Charge Control Mode Wiring
The procedure below is illustrated in
To connect the
C-Series
controller as a charge controller:
1.
Connect the PV array’s positive (+) output to the PV
array disconnect.
2.
Route another (+) cable from the other end of the RE
disconnect to the
PV
GFP
.
3.
Route another (+) cable from the same switch in the PV
GFP to the terminal marked
PV
POS
/
LOAD
in the
C-Series
controller.
4.
Connect the PV array’s negative (–) output to the
terminal marked C
OMMON
N
EGATIVES
.
5.
Connect another negative (-) cable from the other
C
OMMON
N
EGATIVES
to the Negative bus in the DC
disconnect.
6.
Route a negative (–) wire from the PV GFP to the
Negative bus in the DC disconnect.
7.
Connect a positive (+) cable from terminal marked BAT
POS to the battery disconnect in the DC disconnect.
8.
Connect a second positive (+) cable to the other side of
the battery disconnect in the DC disconnect and connect
to the positive (+) battery terminal.
9.
Connect the negative (–) battery cable to the negative bus
in the DC disconnect and tighten the lugs.
10. Tighten per torque requirements outlined on
Allow a little slack on the cables within the controller and
secure the wiring with strain reliefs.
WARNING: Shock Hazard
PV arrays generate voltage whenever light strikes the surface of the
array. Before connecting the
C-Series controller
, cover or
disconnect the array to prevent any current from being generated.