beautypg.com

Load control troubleshooting, Table 4-3, Load control problems – Xantrex Technology C40 User Manual

Page 88

background image

Troubleshooting

68

975-0004-01-02 Rev D

Load Control Troubleshooting

The following table lists possible problems that may arise
when using the

C-Series Multifunction DC Controller

as a

Load Controller.

Table 4-3 Load Control Problems

Problem

Possible Cause

Solution

Load disconnects at
different point than set
for.

A. Load Control decal
is not in place.
B. BTS has been
installed.

A. Install the decal or
follow procedure in
manual. See

“Setting

Voltage Parameters for
Load Control Mode” on
page 24

.

B. Battery Temperature
Sensors should not be used
in load control
applications.

Status LED Blinks
Orange after switching
on the load breaker.

Startup or Inrush
current exceeds
controller rating.

Use larger controller or
“buffer” the controller by
using a relay/contactor
where the controller
operates only the coil of
the relay/contactor and not
directly to the DC load.

This manual is related to the following products: