COOLING CAPACITY - With Air Handler Coils

UNIT

MODEL

AIR HANDLER

COIL

1

MODEL

COOLING

MODEL

W

STAGE

RATED

CFM

NET MBH

SEER

EER

TOTAL

SENSIBLE

18 SEER HP WITH MV - VARIABLE SPEED

YZH02411

MV12B 17 FC/MC43B

1

645

18.2 13.5

16.40

14.00

2 835 23.6 18.8

13.60

MV12D 24 FC/MC48D

1 645 18.5 14.0

17.00

14.50

2 835 24.0 19.5

14.00

MV12D 24 FC/MC60D

1 645 18.5 14.0

17.00

14.50

2 835 24.0 19.5

14.00

YZH03611

MV16C 21 FC/MC43C

1 775 24.8 18.2

17.10

14.20

2 1200 35.4 26.6

13.10

MV16C 21 FC/MC48C

1 775 25.0 18.6

17.30

14.40

2 1200 35.8 26.8

13.35

MV12D 24 FC/MC48D

1 845 24.8 18.0

17.35

14.45

2 1245 35.2 26.2

13.35

MV12D 24 FC/MC60D

1 845 24.8 18.3

17.50

14.60

2 1245 35.4 26.4

13.35

MV12D 24 FC/MC62D

1 845 25.6 19.7

18.00

15.00

2 1245 36.0 27.8

13.35

YZH04811

MV16C 21 FC/MC48C

1 1000 33.4 25.0

16.65

13.60

2 1600 46.5 35.6

12.20

MV20D 24 FC/MC48D

1 1045 33.4 25.0

16.30

13.35

2 1570 46.5 35.6

12.05

MV20D 24 FC/MC60D

1 1045 33.0 25.0

16.20

13.25

2 1570 47.0 36.4

12.25

MV20D 24 FC/MC62D

1 1045 33.8 25.8

17.00

13.90

2 1570 47.0 36.6

12.50

YZH06011

MV20D 24 FC/MC60D

1 1175 39.5 27.6

14.75

12.20

2 1820 57.0 42.0

11.35

MV20D 24 FC/MC62D

1 1175 41.0 29.8

15.50

12.80

2 1820 57.0 43.0

11.80

18 SEER HP WITH AV/SV - VARIABLE SPEED

YZH02411

AV36 21

-

1 600 18.1 13.5

16.65

14.20

2 765 23.4 18.5

13.70

YZH03611

AV36 21

-

1 830 25.2 19.0

17.45

14.55

2 1270 35.4 27.4

13.40

AV/SV48 24

-

1 910 25.8 20.4

17.65

14.70

2 1190 35.4 27.0

13.60

YZH04811

AV/SV48 24

-

1 1135 34.0 26.4

16.75

13.70

2 1610 47.0 36.4

12.30

AV/SV60 24

-

1 1085 33.6 26.0

16.55

13.55

2 1655 47.0 37.0

12.30

YZH06011

AV/SV60 24

-

1 1145 40.5 29.0

15.15

12.50

2 1765 56.5 41.5

11.50

Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210.
Cooling MBH based on 8

0°F entering air temperature, 50% RH, and rated air flow.

EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.

1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.