York YZH024 THRU 060 User Manual
Page 20

20
Unitary Products Group
345094-YTG-D-0108
Multipliers for determining the performance with other indoor section.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
LOW CFM
HEATING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION
OUTDOOR UNIT MODEL NO.
YZH02411
INDOOR COIL MODEL NO.
FC/MC/PC48D + MV12D
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
600
650
700
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
60
60
24.2 1.4 5.2 24.4 1.3 5.4 24.5 1.3 5.6
70
23.9 1.5 4.6 24.0 1.5 4.7 24.1 1.4 4.9
80
23.5 1.7 4.1 23.5 1.6 4.2 23.6 1.6 4.3
47
60
19.8 1.3 4.5 19.8 1.2 4.6 19.8 1.2 4.8
70
19.3 1.4 4.0 19.3 1.4 4.1 19.4 1.4 4.2
80
18.8 1.6 3.6 18.9 1.5 3.6 19.0 1.5 3.7
40
60
17.1 1.2 4.1 17.1 1.2 4.2 17.1 1.2 4.3
70
16.9 1.4 3.7 16.9 1.3 3.7 17.0 1.3 3.8
80
16.7 1.5 3.3 16.7 1.5 3.3 16.8 1.4 3.4
30
60
13.9 1.2 3.5 14.0 1.1 3.6 14.1 1.1 3.7
70
14.0 1.3 3.1 14.0 1.3 3.2 14.0 1.3 3.3
80
14.0 1.4 2.8 13.9 1.4 2.9 13.9 1.4 2.9
17
60
10.5 1.1 2.8 10.9 1.1 2.9 11.4 1.1 3.0
70
10.4 1.2 2.5 10.6 1.2 2.5 10.8 1.2 2.6
80
10.3 1.4 2.2 10.3 1.3 2.2 10.3 1.3 2.3
10
60
9.0 1.1 2.3 9.0 1.1 2.4 9.0 1.1 2.4
70
8.5 1.2 2.1 8.5 1.2 2.1 8.6 1.2 2.2
80
8.0 1.2 1.9 8.1 1.2 1.9 8.2 1.2 2.0
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
MBH
KW
COP
AV36
-
1.00 1.00 1.00
MV12B
FC/MC43B
1.00 1.00 1.00
MV12D
FC/MC60D
1.00 1.00 1.00
Variable Speed
Furnace
Coil
T.C.
S.C.
KW
P(C,V)9*B12
FC/MC/PC43B
0.98 0.98 1.02