Power share, Equalize, Power share –12 equalize –12 – Xantrex Technology MS2000 User Manual
Page 66
Configuration
3–12
975-0125-02-01
Power Share
Configurable setting
Power Share is a configurable setting that you set to match to the breaker rating on
the AC input. This setting is used to ensure that the charger limits its output to try
to prevent nuisance tripping of the AC input breaker due to the total current drawn
by the charger and your other AC loads. See also “Power Share” on page 2–22.
When to use
Set the Power Share setting to match the AC input breaker. Use this setting when
connecting to an AC source. If using multiple AC sources via an AC transfer
switch, adjust this setting to the smaller AC breaker size.
Outcome
Setting the value higher than the AC source’s external breaker could cause the
external breaker to trip.
Equalize
Configurable setting
This setting lets you enable or disable charger equalization, only if the battery type
is flooded (or wet).
Equalization can be turned on (enabled) or off (disabled).
When to use
Review the section, “Operating in Equalization Mode” on page 2–18 before
adjusting this setting. This menu item is displayed if the battery type allows
equalization.
Power Share
[10A]
Range of values
Increment
Default
5 to 50 amps
5 amp increments
30 amps
Equalize
[Off]
Value
Default
On
Off
Off