Charge algorithm graph, Charge algorithm definitions, Figure b-1 – Xantrex Technology MS2000 User Manual
Page 109: Voltage flooded (or wet) gel agm, Current flooded (or wet) gel agm, Time flooded (or wet) gel agm
![background image](/manuals/226538/109/background.png)
Battery Charging Reference for the Main Charger
975-0125-02-01
B–5
Charge Algorithm Graph
Charge Algorithm Definitions
Table B-1 Battery Defaults
Figure B-1 Three-Stage Charging Profile
Voltage
Flooded (or wet) Gel
AGM
V
A
Absorption Voltage (VDC)
14.4
14.4
14.3
V
G
Gassing Voltage (VDC)
13.5
13.8
13.45
V
F1
Float Voltage (VDC)
13.5
13.8
13.45
V
F2
Float Exit Voltage (VDC)
12.5
12.5
12.5
V
E
Equalize Voltage (VDC)
15.5
NA
NA
Current
Flooded (or wet) Gel
AGM
I
B
Bulk Current (ADC)
20% Ah
20% Ah
20% Ah
I
H
Absorption Exit Current (ADC)
2% Ah
2% Ah
2% Ah
I
E
Equalize Current (ADC)
10% Ah
NA
NA
Time
Flooded (or wet) Gel
AGM
∆
T
A
Absorption Timeout (hours)
6
6
6
∆
T
CV
Constant Voltage Absorption Timeout (hours)
1
1
1
I
H
I
B
V
F2
V
F1
V
G
V
A
Float
Time
T
CV
T
A
T
F
Bulk
Absorption