Water heater performance ratings

Boiler

DOE

Heating

Capacity

MBH

First Hour Rating Capacity (GPH) — Boiler Water Supply at 200°F / Domestic Water from 50°F to 115°F

GOLD

Plus

30

Boiler
Water

GPM

Minimum

GOLD/

Ultra

Plus

40

Boiler
Water

GPM

Minimum

GOLD/

Ultra

Plus

60

Boiler
Water

GPM

Minimum

GOLD/

Ultra

Plus

80

Boiler
Water

GPM

Minimum

PLUS

100

Boiler
Water

GPM

Minimum

PLUS

110

Boiler
Water

GPM

Minimum

PLUS

119

Boiler
Water

GPM

Minimum

50

115

8

125

9

130

13

140

20

150

24

170

26

190

28

70

155

160

170

175

185

205

225

90

190

195

205

215

225

245

265

110

230

235

240

250

260

280

300

130

230

260

280

285

300

320

335

150

230

260

315

325

335

355

375

170

230

260

355

360

370

390

410

190

230

260

365

400

410

430

450

210

230

260

365

435

445

465

485

250

230

260

365

510

520

540

560

300

230

260

365

600

610

630

650

350

230

260

365

670

690

725

745

400

230

260

365

670

690

775

835

450

230

260

365

670

690

775

930

500

230

260

365

670

690

775

970

Boiler

DOE

Heating

Capacity

MBH

First Hour Rating Capacity (GPH) — Boiler Water Supply at 200°F / Domestic Water from 50°F to 140°F

GOLD

Plus

30

Boiler
Water

GPM

Minimum

GOLD/

Ultra

Plus

40

Boiler
Water

GPM

Minimum

GOLD/

Ultra

Plus

60

Boiler
Water

GPM

Minimum

GOLD/

Ultra

Plus

80

Boiler
Water

GPM

Minimum

PLUS

100

Boiler
Water

GPM

Minimum

PLUS

110

Boiler
Water

GPM

Minimum

PLUS

119

Boiler
Water

GPM

Minimum

50

90

8

95

9

105

13

115

20

125

18

145

25

165

28

70

120

125

130

140

150

170

190

90

140

150

160

165

180

200

215

110

140

170

185

195

205

225

245

130

140

170

210

220

230

250

270

150

140

170

220

245

260

280

295

170

140

170

220

275

285

305

325

190

140

170

220

300

310

330

350

210

140

170

220

325

340

360

375

250

140

170

220

380

390

410

430

300

140

170

220

410

435

480

495

350

140

170

220

410

435

525

565

400

140

170

220

410

435

525

630

450

140

170

220

410

435

525

630

500

140

170

220

410

435

525

630

For water heater to achieve the rated performance below: Boiler water must be supplied to the water heater at

at least 200°F, and the boiler water flow rate must be no less than given in the tables below. For

Gas boiler

applications, with supply water at 190°F, see the ratings in Section B of this manual)

F