General piping

information

• For domestic water piping, see pages 8 through 12.
• See pages 22–2, for domestic water recirculation piping.
• See Table 1 for piping connections:

• All plumbing must meet or exceed all local, state and national plumbing codes.
• Use pipe dope or tape suitable for potable water.
• Use isolation valves to isolate system components.

• See Section B for

Gas boiler and system piping or Sections C boiler and system piping

with other boilers.

Water hammer

Dishwashers, clothes washers, and fast-closing positive shutoff valves incorporated in the system

all contribute to creating water shock. Install a water hammer arrester to prevent damage to pipes

and appliances. See control manufacturer’s instructions for application and installation.

Thermal expansion

If a backflow preventer, check valve, or pressure reducing valve is piped

on cold water inlet of water heater, you must install an expansion tank on

cold water supply line to prevent normal thermal expansion from repeat-

edly forcing open T&P relief valve. The T&P relief valve is not intended

for constant duty, such as relief of pressure due to repeated normal system

expansion.

Refer to expansion tank manufacturer’s instructions for proper sizing.

Failure to follow the above could result in severe personal injury, death or

substantial property damage.

Table 1

Piping (Inches NPT)

Water
Heater
Model

Connections

Recommended

Piping Between

Water Heater

and Boiler

Recirculation Dip Tube

Domestic

Water

Inlet/Outlet

Boiler Water

Supply/

Return

Length

(inches)

Diameter

(inches)

30

¾

1

1

34

¾

40

¾

1

1

42

¾

60

¾

1 ¼

1 ¼

52

¾

80

¾

1 ¼

1 ½

61

¾

100

1 ½

1 ½

1 ½

25

1 ½

110

1 ½

1 ½

1 ½

32

1 ½

119

1 ½

2

2

32

1 ½

Water heater piping

continued

If domestic water-side pressure exceeds 70 psig, install a pressure

reducing valve to prevent pressure spikes. Higher pressures can cause the

heater pressure/temperature valve to lift or weep.

A2