configured for a specific zone and includes the passback feature. In addition, the MOR and the
SE 6000 keep track of the people that are in a specified zone.
E
NTERING
A
M
ULTIPLE
O
CCUPANCY
Z
ONE
When a multiple occupancy zone is vacant, two keyholders are required to present their keys to
the reader to unlock the door; first one and within a prescribed time period, the other, unlocking
the door. Once three or more people are in the multiple occupancy zone, the reader works like a
standard reader, that is, as an individual keyholder with rights presents their key, the door is
unlocked, either entering or leaving.
V
ACATING
A
M
ULTIPLE
O
CCUPANCY
Z
ONE
Vacating a Multiple Occupancy zone, requires that the last two keyholders present their keys at
the same time, first one and then within the prescribed time period the other, unlocking the door.
R
EADER
R
EPORT
D
EFINITION
S
CREENS
The reader report definition screens, [rdr1entr], [rdr2entr], [rdr3entr], and [rdr4entr] are used,
respectively, when setting up a reader to operate with an SE 8xx-series, 422, or NexSentry ACU.
Press F2 after storing the data on the [rdr_entr] screen; the appropriate second screen
automatically displays.
SE 8
XX
-S
ERIES
R
EADER
R
EPORT
D
EFINITION
[rdr1entr]
Reader Mode. Optional. Enter the appropriate reader mode number. This is used for
building modes. The default is 0.
0 = Normal, 1 = Open, 2 = Closed, 3 = Station
The remaining fields, Forced Open through Exit Denied, require a report number entry. The word
report in this context identifies a user-defined action or series of actions that the ACU is to take