GOLD CGs Gas-Fired Water Boiler — Boiler Manual

11d

Troubleshooting — control module lights

(cont.)

• Turn off power to the boiler at service switch or breaker.

• Wait at least 45 seconds.

• Turn on power to boiler.

• Restart boiler, following

Operating instructions in this

manual (Section

9c).

• Look through the pilot inspection port (in front of air inlet

box) to see if the pilot is burning during the prepurge

period (first 30 seconds of operation).

Is pilot burning during prepurge period?

CHART 4 — FLAME & POWER lights flashing

Electrical shock hazard — Wherever you see

TURN OFF POWER , follow the instructions. Failure to follow

instructions could result in severe personal injury, death or substantial property damage.

• Leave main manual gas valve closed.

• Turn off power to boiler at service switch or breaker.

• Wait at least 45 seconds.

• Turn on power to boiler.

• Restart boiler, following

Operating instructions in this

manual (Section

9c).

Do

FLAME and POWER lights still flash?

• Boiler should now

operate normally.

• Original flashing

FLAME light

caused by gas

valve not

operating properly.

• See normal

sequence of

operation,

Figure 18,

page 31.

• Replace gas valve.

• Retest boiler.

Are

FLAME and POWER lights flashing?

No

Yes

No

Yes

Are manual main shutoff valve and gas valve open?

• Replace control module.

• Retest.

— Usually indicates flame sensed when it shouldn't be there —

Yes

No

TURN OFF POWER

to boiler at service switch

or breaker.

• Open main manual gas

valve.

• Turn on power to boiler

at service switch or

breaker.

• Restart boiler per lighting

instructions.

• Perform start-up

procedures in boiler

manual to verify proper

operation.

• Allow boiler to continue cycling.

Are

FLAME & POWER lights flashing?

No

Yes

No

Yes

• Replace control

module.

• Retest.

• Replace control

module.

• Retest.

• Boiler may now be

operating

normally.

• Perform start-up

procedures in

boiler manual to

verify proper

operation.