beautypg.com

Start-up — operate boiler, Start-up — if boiler doesn’t start – Weil-McLain GOLD CGS 550-110-260/0107 User Manual

Page 29

background image

Part number 550-110-260/0107

9

GOLD CGs Gas-Fired Water Boiler — Boiler Manual

Start-up — operate boiler

(continued)

7b

Figure 16 Typical pilot burner flame

Figure 17 Typical main burner flame

Check burner flames

View pilot and main flames through the inspection port

in the Air inlet box front cover.

Pilot burner flame

(

Figure 16

)

PROPER pilot flame characteristics

1. Blue flame.
. Inner cone engulfing pilot flame sensor.
3. Pilot flame sensor glowing cherry red.

IMPROPER pilot flame characteristics:

1. Overfired — Large flame lifting or blowing past pilot

flame sensor.

. Underfired — Small flame. Inner cone not engulfing

pilot flame sensor.

3. Lack of primary air — Yellow flame tip.
4. Incorrectly heated pilot flame sensor.

Main burner flame

(

Figure 17

)

PROPER main burner flame characteristics

1. Yellow-orange streaks may appear (caused by

dust).

IMPROPER main burner flame characteristics

1. Overfired — Large flames.
. Underfired — Small flames.
3. Lack of primary air — Yellow tipping on flames

(sooting will occur).

Start-up — if boiler doesn’t start . . .

7c

1. Loose connections, blown fuse or service switch

off?

. High limit switch set below boiler water tempera-

ture?

3. Thermostat set below room temperature?
4. Gas not turned on at meter or boiler?

5. Incoming gas pressure less than:

5” w.c. for natural gas?

11” w.c. for propane gas?

6. If none of the above corrects the problem, refer to

Troubleshooting

, Section

11

of this manual.

If you discover evidence of any gas leak, shut down the
boiler at once. Find the leak source with bubble test and
repair immediately. Do not start boiler again until cor-
rected. Failure to comply could result in severe personal
injury, death or substantial property damage.

Check for: