beautypg.com

Field wiring, Gold cgs gas-fired water boiler — boiler manual, Thermostat – Weil-McLain GOLD CGS 550-110-260/0107 User Manual

Page 26: Junction box (furnished), Electrical installation must comply with, Wiring connections

background image

Part number 550-110-260/0107

6

GOLD CGs Gas-Fired Water Boiler — Boiler Manual

Field wiring

6

Thermostat

1. Connect thermostat as shown on wiring diagram

on boiler.

.

Install on inside wall away from influences of

drafts, hot or cold water pipes, lighting fixtures,

television, sunrays, or fireplaces.

3. If thermostat has a heat anticipator, set heat antici-

pator in thermostat to match power requirements

of equipment connected to it. If connected directly

to boiler, set for 0.4 amps. For other devices, refer

to manufacturer’s specifications. Wiring diagram

on boiler gives setting for control module and gas

valve. Also see instructions with thermostat.

Junction Box (furnished)

1. Connect 10 VAC power wiring as shown in

Figure 15

.

. Fused disconnect or service switch (15 amp. recom-

mended) may be mounted on this box. For those

installations with local codes which prohibit installa-

tion of fused disconnect or service switch on boiler,

install a x 4 cover plate on the boiler junction box

and mount the service switch remotely as required

by the code.

For your safety,

turn off electrical power supply at

service entrance panel before making any electrical

connections

to avoid possible electric shock hazard.

Failure to do so can cause severe personal injury or

death.

Wiring must be N.E.C. Class 1.

If original wiring as supplied with boiler must be re-
placed, use only type

105°C

wire or equivalent.

Boiler must be

electrically grounded

as required by

National Electrical Code ANSI/NFPA 0 – latest edi-

tion.

Electrical installation must
comply with:

1. National Electrical Code and any other national,

state, provincial or local codes or regulations.

. In Canada, CSA C.1 Canadian Electrical Code

Part 1, and any local codes.

Wiring connections

Boiler is shipped with controls completely wired.

Figure 15

Field wiring connections —

service switch and thermostat

(or end switch)

provided by installer

The CGs control module is polarity-sensitive. The hot and neutral wires must be connected to

the correct leads. A flashing POWER light usually indicates reversed polarity of 10 VAC lead

wires.