Piping — low temp systems, Gold cgs gas-fired water boiler — boiler manual – Weil-McLain GOLD CGS 550-110-260/0107 User Manual
Page 19
Part number 550-110-260/0107
19
GOLD CGs Gas-Fired Water Boiler — Boiler Manual
1
Boiler isolation (balancing) valves
2
Flow/check valve
3
System or zone circulator
4
System temperature gauges
5
Zone valve
6
Drain valve
7
System temperature valves (see instruc-
tions to the left for adjusting valves)
8
Blend temperature gauge
9
Relief valve
10
Automatic air vent (with diaphragm-type expansion tank), or
connect to tank fitting (closed-type expansion tank).
DO NOT
use an automatic air vent when using closed-type expansion
tank. It would allow air to leave the system, causing waterlog-
ging of the expansion tank.
11
Fill valve
12
Diaphragm-type or bladder-type expansion tank, if used (For
closed-type expansion tank, pipe from top of air separator to
tank fitting as in
Figure 5
, page 15.)
13
Air separator and automatic vent, if used (Note that the
fill valve must always be connected to the expansion tank,
regardless of location of expansion tank, circulator or air
separator.)
Figure 8
Primary/secondary piping
Zoning with circulators
Figure 9
Primary/secondary piping
Zoning with zone valves
3d
Piping — low temp systems
(continued)