beautypg.com

Piping — low temp systems, Gold cgs gas-fired water boiler — boiler manual, Primary/secondary – Weil-McLain GOLD CGS 550-110-260/0107 User Manual

Page 18: Bypass piping method

background image

Part number 550-110-260/0107

18

GOLD CGs Gas-Fired Water Boiler — Boiler Manual

Piping — low temp systems

3d

Failure to

prevent low return water temperature

to the boiler could cause corrosion of

the boiler sections or burners, resulting in severe personal injury, death or substantial
property damage.

Radiant heating system piping should include a means of

regulating the boiler return

water temperature

and the

system supply temperature

(such as provided by an

injec-

tion pumping control

).

Boiler return water temperature will be adequately controlled using the methods shown

in this manual provided the

system supply temperature

is

relatively constant.

DO NOT

apply the methods of this manual if the system is equipped with an

outdoor

reset control.

Instead,

provide controls and piping

which can

regulate the boiler re-

turn water temperature

at

no less than 130°F

regardless of system supply temperature.

Contact your Weil-McLain representative for suggested piping and control methods.

Failure to

prevent cold return water temperature

to the boiler could cause corrosion

damage to the sections or burners, resulting in possible severe personal injury, death or
substantial property damage.

Primary/secondary

(preferred)

bypass piping method

Primary/secondary

bypass piping is preferred because

the flow rate and temperature drop in the heating
circuit(s) is determined only by the heating circuit
circulator(s). So adjustment of the bypass valves in
the boiler circuit will not cause a change in the heating
circuit rate and temperature distribution.

Figures 8

and

9

, page 19, show suggested bypass ar-

rangements using

primary/secondary

bypass piping

(preferred) for low temperature systems such as

radiant

heating systems

or

converted gravity systems

. For

alternatives, see pages 0 through 3.

The bypass valves in

Figures 8

and

9

(items

7a

and

7b

)

provide mixing of hot boiler outlet water with cooler
system return water — set to assure a minimum return
water temperature (at least 130°F) to the boiler. Set the
valves as explained below.

Temperature gauges

Gauge

4a

is suggested, but optional on any system.

Gauge

4b

is optional on converted gravity systems,

but

required

on radiant heating systems — to display

the water temperature being supplied to the radiant
tubing.

Gauge

8

is

required

on all systems to assure the return

water temperature is accurately set for a minimum of
130°F. If this gauge is not available however, adjust the
valves such that the boiler-mounted temperature/pres-
sure gauge reads at least 150°F when the system return
water is cold (approximately 60°F water temperature).

Valve adjustment
(Figures 8 and 9 only)

1. Set the valves while the system is cool, setting for the

coldest expected water temperature (usually 60°F
since the system will often drop to room tempera-
ture between cycles).

. Start with valve

7a

fully closed and

7b

fully open.

3. Gradually open valve

7a

while closing valve

7b

until

the temperature at gauge

8

reads 130°F when gauge

4a

reads 60°F.

4. Note that valve

7a

regulates the amount of hot wa-

ter from the boiler supply which mixes with return
water. Valve

7b

regulates the amount of system water

flowing through the boiler secondary loop.