beautypg.com

How it works – Weil-McLain GOLD CGS 550-110-260/0107 User Manual

Page 2

background image

Part number 550-110-260/0107

GOLD CGs Gas-Fired Water Boiler — Boiler Manual

How it works . . .

Control module

The control module responds to signals from the room thermostat, air pressure switch and

boiler limit circuit to operate the boiler circulator, pilot burner, gas valve and inducer. When

room thermostat calls for heat, the control module starts the system circulator and inducer.
The control module runs the inducer long enough to purge the boiler flue passages, then opens

the pilot valve and activates pilot ignition spark.
The control module allows up to 15 seconds to establish pilot flame. If flame is not sensed

within 15 seconds, the control module will turn off the gas valve, flash the Flame light, and

then enter a 15-second postpurge. The control module will then start a new cycle. This will

continue indefinitely until pilot flame is established or power is interrupted. Once pilot flame

is proven, the control module opens the gas valve to allow main burner flame.
When the room thermostat is satisfied, the control module turns off the gas valve, operates the

inducer for a 15-second postpurge and waits for the next heat call.
The control module indicator lights show normal sequence when the lights are on steady. When
a problem occurs, the control module flashes combinations of lights to indicate the most likely
reason for the problem (see page 45).

Transformer

The control transformer reduces line voltage to 4 volts for the gas valve and limit circuit.

Inducer

The inducer pulls flue gases through the boiler, causing air to be pulled in through the air intake

opening. The inducer pushes the flue gases through the vent pipe as well.

Air pressure switch

The air pressure switch signals the control module, telling the control module whether air is

moving through the inducer.

Water temperature limit switch

The water temperature limit switch turns off the gas valve if the temperature in the boiler goes
above its setting. (The circulator will continue to run as long as there is a call for heat.)

Boiler circulator

The boiler circulator circulates water through the external (system) piping. The circulator is
shipped loose, and can be mounted on either the boiler supply or return piping. The factory-
installed circulator wiring harness provides ample length for either location.

NOTE

— The

control module provides a pump exercising routine. If the boiler is not operated for 30 days,
the control module will power the circulator for 30 seconds, then turn off.

a supply to system
b return from system
c combustion air inlet
d flue outlet
e gas valve

f pressure/temperature gauge
g relief valve (not visible)
h air vent connection
i flame rollout switch
j air inlet box

k pilot burner and bracket
l stainless steel burners
m cast iron boiler sections
n flue collector
o junction box

Other boiler components: