beautypg.com

Class b wiring, Class b wiring -8, Figure 6-5. class b (string) wiring -8 – Tyco 4100U-S1 User Manual

Page 96: Wiring to idnet devices, Continued

background image

6-8


To connect the IDNet card to devices using Class B wiring, read the following
instructions.

1. On TB1, jumper IDNetB+ to IDNet A+, and jumper IDNetB- to IDNetA-. If the

jumper is absent, a Class A Trouble will be indicated on LED 2.

2. Route wire from the IDNetA+, IDNetA-, (or B+, B-) outputs on TB1 of the

IDNet card to the first device, then on to the following devices.

3. Up to 40 devices maximum.

4. Sounder bases or 6 Point I/O modules in separate zones may not be wired in

Class B (string).

The illustration below shows Class B wiring.

+

1

2

1

2

1

2

1

2

Figure 6-5. Class B (string) Wiring


Note:
Maintain correct polarity on terminal connections. Do not loop wires

under terminals.

Wiring to IDNet Devices,

Continued

Class B Wiring

IDNET CARD

IDNET DEVICES

0.75 mm

2

and 4 mm

2

FERRITE BEAD (see fig 5.1)