G-1
System Capacity
500 points of addressable devices, plus 500 points of
annunciation.
Expansion
up to 4 x 4100 legacy cards
up to 4 x 4” x 5” PDI cards
Cabinet Size
1050H x 550W x 280D (mm)
Cabinet Material
1.2mm Zintec
Cabinet Finish
Powder coated
Cabinet Colour
Cream Wrinkle external, flat black internal trim
Mounting Wall
mount
Mains Input
240V AC, +6%, -10%, 50Hz
Internal Power Supply
24V DC @ 9A
Standby Battery
24V sealed lead acid type up 40Ah
Battery Charger
27.3V DC (nominal)
PSU Supervision
Charger high/low, Battery low/fail
Temperature
-5
°C to 45°C
Humidity
10% to 90% RH non-condensing
Refer to Table 4-1 and 4-2 for full SPS specifications.
Alarm Relay Card
F1 Alarm, 3A, 15 x 5mm, Glass Cartridge
F2 Supervisory, 3A, 15 x 5mm, Glass Cartridge
F3 Trouble, 3A, 15 x 5mm, Glass Cartridge
Fused Distribution Board
F1 24V Out, 1A 20 x 5mm Glass Cartridge
F2 24V Out, 1A 20 x 5mm Glass Cartridge
F3 24V Out, 1A 20 x 5mm Glass Cartridge
F4 24V Out, 1A 20 x 5mm Glass Cartridge
•
WALK TEST System Test
•
4 Operator Access Levels
•
Event Historical Logging
•
Device selectable Alarm Verification
•
Individual Zone Isolate
•
Addressable device disable/enable
•
Non-volatile Flash EPROM for field editable program changes
•
Expansion cards firmware upgraded via download to flash EPROMs
Appendix G
4100U-S1 Specifications
General
Fuses
Firmware Features