T-gen 50 settings for nac operation, T-gen 50 settings for nac operation -12 – Tyco 4100U-S1 User Manual
Page 80

5-12
These switch and link settings should be used. These apply to T-GEN 50 software
version 1.7.
Alert to Evacuate
Change-Over Time
SW1
(T0)
SW2 (T1)
SW3
(T2)
Setting on T-GEN 50
OFF OFF OFF
0
sec
ON OFF OFF
30
sec
OFF ON OFF
1
min
ON ON OFF
1.5
min
OFF OFF ON
3
min
ON OFF ON
5
min
OFF ON ON
10
min
ON ON ON
Alert
Only
SW1 to SW3 settings have no effect on Slave T-GEN 50s.
SWITCH
Name
Setting on T-GEN 50
SW4 ALM
I/P
Supervision
OFF (Supervision disabled)
SW5
ALM I/P
OFF (Non-latching)
SW6 OFF
SW7
Evac Tone
OFF for AS 2220 tone
ON for ISO 8201 + Keywords
SW8
Evac Message
OFF for Evac Message 1 or Field
Recorded message,
ON for Evac Message 2 or Keywords
only in ISO 8201
Link
Name
Setting on T-GEN 50
1
BIAS
Can be FITTED if PA or Background
Music not required
2 MASTER
FITTED
3
REC EN
Fit to record message.
4
TEST
Fit for test tone during installation
5 SLAVE
NOT
FITTED
6
SLAVE / MASTER
MASTER
7 FAULT=
DEF-/RELAY
RELAY
Using T-Gen 50 with 4100U-S1,
Continued
T-Gen 50 Settings for
NAC Operation