Table 6-2 Cable Run Lengths


1. The current allowance per device on the loop is 0.5mA with the LED off, 2mA with

the LED on. A maximum of 20 LEDs will be turned on at any time by the IDNet

Card, e.g. in alarm.


2. The minimum voltage allowed at the furthest device to guarantee operation is

24.9Vdc. The IDNet boosts its output voltage from 30V to 35V during alarm.


To connect the IDNet card to devices using Class A wiring, read the following
instructions and refer to the figure below.

1. Route wire from the IDNetB+, IDNetB- outputs on TB1 of the IDNet card to
the appropriate inputs on a peripheral IDNet device.

2. Route wire from the first IDNet device to the next one. Repeat for each
device.

3. Route wire from the last IDNet device to the IDNetA+ and IDNetA- inputs on

TB1 of the IDNet card.


4. Separate every 40 devices (at most) with a communications isolator, e.g. 4090-
9116.

5. Separate the power feed to sounder bases or 6 point I/O modules in different zones
using the 4090-9117 Power Isolate module.

+

1

2

1

2

1

2

Figure 6-4. Class A (loop) Wiring

Continued on next page

Wiring to IDNet Devices,

Continued

Wire Size

0.75 mm

2

1

mm

2

1.5

mm

2

2.5

mm

2

4

mm

2

Resistance

Distance

385 m

513 m

769 m

1,282 m

2,052 m

20

Ω

Distance

769 m

1,026 m

1,538 m

2,565 m

4,104 m

40

Ω

Notes

Class A Wiring

IDNET CARD

IDNET DEVICES

0.75

mm

2

to 4

mm

2

SHIELD

SHIELD

FERRITE BEAD

FERRITE BEAD
(see figure 5.1)