Appendix h 4100u specifications, General, Fuses – Tyco 4100U User Manual
Page 174: Firmware features

H-1
System Capacity
2,000 points of addressable points, plus 2,000 points of
annunciation. Expansion
Up to capacity above.
Up
to
119
Addressable
cards
Cabinet
Size
Dependent
on
system
configuration
Cabinet Material
1.6mm Zintex
Cabinet Finish
Powder coated
Cabinet Colour
Cream Wrinkle
Mounting Wall
mount
Mains Input
240V AC, +6%, -10%, 50Hz
Internal Power Supply
24V DC @ 9A
Standby Battery
24V sealed lead acid up 110Ah
Battery Charger
27.3V DC (nominal)
PSU Supervision
Charger high/low, Battery low/fail
Temperature
-5
°C to 45°C
Humidity
10% to 90% RH non-condensing
Refer to Table 6-1, 6-2 for full SPS specifications.
Alarm Relay Card
F1 Alarm, 3A, 15 x 5mm, Glass Cartridge
F2 Supervisory, 3A, 15 x 5mm, Glass Cartridge
F3 Trouble, 3A, 15 x 5mm, Glass Cartridge
Fused Distribution Board (if fitted)
F1 24V Out, 1A 20 x 5mm Glass Cartridge
F2 24V Out, 1A 20 x 5mm Glass Cartridge
F3 24V Out, 1A 20 x 5mm Glass Cartridge
F4 24V Out, 1A 20 x 5mm Glass Cartridge
•
WALK TEST System Test
•
4 Operator Access Levels
•
Event Historical Logging
•
Device selectable Alarm Verification
•
Individual Zone Isolate
•
Addressable device disable/enable
•
Non-volatile Flash EPROM for field editable program changes
•
Expansion cards firmware upgraded via download to flash EPROMs
Appendix H
4100U Specifications
General
Fuses
Firmware Features