beautypg.com

Compatible detectors, idnet, List of approved devices – Tyco 4100U User Manual

Page 171

background image

F-4

Simplex MAPNET 2 Range – Addressable Field Devices

2190-9156

Mapnet 2 Monitor ZAM

2190-9162

Mapnet 2 Signal ZAM

2190-9164

Mapnet 2 Control ZAM

2190-9169

Mapnet 2 Line Powered Short Circuit Isolator

2190-9172

Mapnet 2 Supervised IAM

2190-9173

Mapnet 2 Loop powered 2 Point Input / Output

Module

4099-9032NL

Mapnet 2 Addressable Manual Call Point



The following lists the detectors approved for use with IDNet and shows current
rating and numbers allowed per loop.

Device Type

Operating

Current mA

Maximum

Number Allowed

Per Loop

Maximum

Number

Allowed Per

Line

4098-9714E

Analogue Photoelectric

Smoke Detector

0.5

(2 with LED

on)

250 40*

4098-9717E

Analogue Ionisation

Smoke Detector

0.5

(2 with LED

on)

250 40*

4098-9733E

Analogue Heat Type A &

B Detector

0.5

(2 with LED

on)

250 40*

4098-9754E

Analogue Multi

(Heat/Photo)

Detector

0.5

(2 with LED

on)

250 40*


* Maximum allowed by AS1670.1.

The above with 9714E, 9717E and 9733E use a (4098-) 9789E addressable base
or 9794E addressable sounder base, or 9793 addressable isolator base. The
9754E uses a 9796E addressable base or 9795E sounder base.

The maximum specified loop/line resistance is 40

Ω.


The maximum number of LEDs switched on by an IDNet in alarm is 20.



List of Approved Devices,

Continued

Compatible Detectors, IDNET