Make sure these guidelines are accounted for before wiring:

• All field wires must be 0.75 mm

2

or greater and comply with AS1670.1 and the

wiring code.

• Conductors must test free of all grounds.
• All wiring must be done using copper conductors only, unless noted otherwise.
• If shielded wire is used,

-

the metallic continuity of the shield must be maintained throughout the
entire cable length.

-

the entire length of the cable must have a resistance greater than 1 Megohm
to earth ground.

• Underground wiring must be free of all water.
• In areas of high lightning activity, or in areas that have large power surges, the

2081-9027 Transient Suppressor should be used on monitor points.

• Wires that run in plenum should be in conduit.
• A system ground must be provided for earth detection and lightning protection

devices. This connection must comply with approved earth detection.

• Only system wiring should be run together in the same conduit.
• Use supplied ferrite beads with all SPS field wiring including the Aux 24V.

Loop wires twice through the supplied ferrite bead(s) as shown in Figure 7-1.
(Extra can be ordered as SX0005.)

Figure 7-1. The Ferrite Bead (SX0005)