Class b wiring, Class b wiring -9, Figure 8-6 – Tyco 4100U User Manual

Page 131: Wiring to idnet devices, Continued

background image

8-9


To connect the IDNet card to appliances using Class B wiring, read the following
instructions.

1. On TB1, jumper IDNetB+ to IDNet A+, and jumper IDNetB- to IDNetA-. If the

jumper is absent, a Class A Trouble will be indicated on LED 2.

2. Route wire between 0.75 mm

2

and 4 mm

2

from the IDNetA+, IDNetA-, (or B+,

B-) outputs on TB1 of the IDNet card to a junction box. Begin “T” tapping at the
junction box.

3. Up to 40 devices maximum.

4. Sounder bases or 6 Point I/O modules in separate zones may not be wired in
Class B.

The illustration below shows Class B wiring.

+

1

2

1

2

1

2

1

2

Figure 8-6. Class B Wiring


Note:
Maintain correct polarity on terminal connections. Do not loop wires

under terminals.

Wiring to IDNet Devices,

Continued

Class B Wiring

IDNET CARD

IDNET DEVICES

0.75 mm

2

and 4 mm

2

FERRITE BEAD (see fig 7.1)