Class b nac wiring table, Class b nac wiring table -7, Power supply wiring distances – Tyco 4100U User Manual
Page 115

7-7
Table 7-2 lists the maximum distances from the NAC terminal block to the last appliance
in a Class B configuration, depending on wire gauge and current. Use Table 7-2 to
calculate wire distances for your application if you are using Class B wiring.
Table 7-2. Class B Wiring Distances
Alarm
Current @
24 V
Max Distance
w/ 18 AWG
(0.8231 mm
2
)
Max Distance
w/ 16 AWG
(1.309 mm
2
)
Max Distance
w/ 14 AWG
(2.081 mm
2
)
Max Distance w/
12 AWG
(3.309 mm
2
)
DC
Resistance
0.25 A
840 ft. (256 m)
1,335 ft. (407 m) 2,126 ft. (648 m) 3,382 ft. (1,031 m)
12 Ohms
0.50 A
420 ft. (128 m)
667 ft. (203 m)
1,063 ft. (324 m)
1,691 ft. (515 m)
6 Ohms
0.75 A
280 ft. (85 m)
445 ft. (136 m)
709 ft. (216 m)
1,127 ft. (344 m)
4 Ohms
1 A
210 ft. (64 m)
334 ft. (102 m)
532 ft. (162 m)
845 ft. (258 m)
3 Ohms
1.25 A
168 ft. (51 m)
267 ft. (81 m)
425 ft. (130 m)
676 ft. (206 m)
2.4 Ohms
1.50 A
140 ft. (43 m)
222 ft. (68 m)
354 ft. (108 m)
564 ft. (172 m)
2 Ohms
1.75 A
120 ft. (37 m)
191 ft. (58 m)
304 ft. (93 m)
483 ft. (147 m)
1.71 Ohms
2 A
105 ft. (32 m)
167 ft. (51 m)
266 ft. (81 m)
423 ft. (129 m)
1.5 Ohms
2.25 A
93 ft. (28 m)
148 ft. (45 m)
236 ft. (72 m)
376 ft. (115 m)
1.33 Ohms
2.50 A
84 ft. (26 m)
133 ft. (41 m)
213 ft. (65 m)
338 ft. (103 m)
1.2 Ohms
2.75 A
76 ft. (23 m)
121 ft. (37 m)
193 ft. (59 m)
307 ft. (94 m)
1.09 Ohms
3 A
70 ft. (21 m)
111 ft. (34 m)
177 ft. (54 m)
282 ft. (86 m)
1 Ohm
Notes:
• Max Distance = distance from SPS or RPS to last appliance.
• This table is calculated at 49 degrees Centigrade (120 degrees
Fahrenheit). If you are installing in locations that could be exposed to
higher temperatures, refer to NEC Table 7 and 8 in NFPA code, or
applicable local standard.
• Distances are based on a 3 V drop, and take into account the worst-case
panel output voltage. These distances are worst case to allow for one
single load at the furthest point.
• If circuit integrity wire is used instead of housing cable in a fire rated
enclosure, reduce wiring distances by 38 feet (12 m) for every 10 feet (3
m) of potential exposure.
• For other wire gauges (e.g. 4 mm
2
) multiply the distance specified for the
nearest wire size by the ratio of the wire area, e.g. for 3A on 4 mm
2
look
up 3A on 12AWG (3.3 mm
2
) and multiply the resulting 86m x 4.0/3.3 =
104m.
Continued on next page
Power Supply Wiring Distances,
Continued
Class B NAC
Wiring Table