Output parameters, Operation panel parameters – Toshiba VF-S11 User Manual
Page 62

E6581160
61
7
• Output parameters
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
E6581158
H
0669
Logic output/pulse
train output
selection (OUT-
NO)
-
-
0: Logic output
1: Pulse train output
0
6.20.1
H
0676
Pulse train output
function selection
(OUT-NO)
-
-
0: Output frequency
1: Output current
2: Set frequency
3: DC voltage
4: Output voltage command value
5: Input power
6: Output power
7: Torque
8: Torque current
9: Motor cumulative load factor
10: Inverter cumulative load factor
11: PBR (braking reactor) cumulative
load factor
12: Frequency setting value (after
PID)
13: VIA/II Input value
14: VIB Input value
15: Fixed output 1 (Output current:
100%)
16: Fixed output 2 (Output current:
50%)
17: Fixed output 3
(Other than the output current:
100%)
0
6.20.1
H
0677
Maximum numbers
of pulse train
pps
1/1
500-1600
800
6.20.1
H
0691
Inclination
characteristic of
analog output
-
-
0: Negative inclination (downward
slope)
1: Positive inclination (upward slope)
1
6.20.2
H
0692
Meter bias
%
1/1
0-100
0
6.20.2
• Operation panel parameters
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
E6581158
H
0700
Prohibition of
change of
parameter settings
-
-
0: Permitted
1: Prohibited
0
6.21.1
H
0701
Unit selection
-
-
0: %
1: A (ampere)/V (volt)
0
6.21.2
H
0702
Free unit selection
Times
0.01/0.01
0.00: Free unit display disabled
(display of frequency)
0.01-200.0
0.00
H
0705
Inclination
characteristic of
free unit display
-
-
0: Negative inclination (downward
slope)
1: Positive inclination (upward slope)
1
H
0706
Free unit display
bias
Hz
0.01/0.01
0.00-HJ
0.00
6.21.3
H
0707
Free step 1
(pressing a panel
key once)
Hz
0.01/0.01
0.00: Disabled
0.01-HJ
0.00
H
0708
Free step 2 (panel
display)
-
1/1
0: Disabled
1-255
0
6.21.4