Toshiba VF-S11 User Manual
Page 61
E6581160
60
7
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
E6581158
H
0609
Small current
detection current
hysteresis
%
1/1
1-20
10
H
0610
Small current
trip/alarm
selection
-
-
0: Alarm only
1: Tripping
0
H
0611
Small current
detection current
%
(A)
1/1
0-100
0
H
0612
Small current
detection time
s
1/1
0-255
0
6.19.7
H
0613
Detection of
output short-circuit
during start-up
-
-
0: Each time (standard pulse)
1: At start-up (only one time after
power is turned on)
(standard pulse)
2: Each time (short-time pulse)
3: At start-up (only one time after
power is turned on)
(short-time pulse)
0
6.19.8
H
0615
Over-torque
trip/alarm
selection
-
-
0: Alarm only
1: Tripping
0
H
0616
Over-torque
detection level
%
1/1
0-250
150
H
0618
Over-torque
detection time
s
0.1/0.1
0.0-10.0
0.5
6.19.9
H
0619
Over-torque
detection level
hysteresis
%
1/1
0-100
10
6.19.9
H
0621
Cumulative
operation time
alarm setting
100
Time
0.1/0.1
(=10 hours)
0.0-999.9
610
6.19.10
H
0626
Over-voltage stall
protection level
%
1/1
100-150
*1
6.13.5
H
0627
Undervoltage
trip/alarm
selection
-
-
0: Alarm only
(detection level below 60%)
1: Tripping
(detection level below 60%)
2: Alarm only
(detection level below 50%,
DC reactor necessary)
0
6.19.12
H
0633
Trip at VIA low
level input mode
%
1/1
0: Disabled, 1-100
0
6.19.13
H
0634
Annual average
ambient
temperature (parts
replacement
alarms)
-
-
1: -10 to +10
°C
2: 11-20
°C
3: 21-30
°C
4: 31-40
°C
5: 41-50
°C
6: 51-60
°C
3
6.19.14
*1 : Default values vary depending on the capacity. See the table of 64.