beautypg.com

3 control circuit terminals – Toshiba VF-S11 User Manual

Page 14

background image

E6581160

13

2

Wire size (See Note 4)

Voltage class

Capacity of

applicable

motor (kW)

Inverter model

Power circuit

(mm

2

) (Note 1.)

DC reactor

(optional) (mm

2

)

Braking resistor/

Braking unit

(optional) (mm

2

)

Earth cable

(mm

2

)

0.4

VFS11-4004PL

2.0 (2.0)

2.0

2.0

3.5

0.75

VFS11-4007PL

2.0 (2.0)

2.0

2.0

3.5

1.5

VFS11-4015PL

2.0 (2.0)

2.0

2.0

3.5

2.2

VFS11-4022PL

2.0 (2.0)

2.0

2.0

3.5

4.0

VFS11-4037PL

2.0 (2.0)

2.0

2.0

3.5

5.5

VFS11-4055PL

2.0 (2.0)

3.5

2.0

3.5

7.5

VFS11-4075PL

3.5 (2.0)

5.5

2.0

3.5

11

VFS11-4110PL

5.5 (2.0)

8.0

2.0

5.5

Three-phase
500V class

15

VFS11-4150PL

8.0 (5.5)

14

3.5

5.5

0.75

VFS11-6007P

2.0

2.0

2.0

3.5

1.5

VFS11-6015P

2.0

2.0

2.0

3.5

2.2

VFS11-6022P

2.0

2.0

2.0

3.5

4.0

VFS11-6037P

2.0

2.0

2.0

3.5

5.5

VFS11-6055P

2.0

2.0

2.0

3.5

7.5

VFS11-6075P

2.0

2.0

2.0

3.5

11

VFS11-6110P

3.5

3.5

2.0

3.5

Three-phase
600V class

15

VFS11-6150P

5.5

5.5

2.0

5.5

Note 1: Sizes of the wires connected to the input terminals R/L1, S/L2 and T/L3 and the output terminals U/T1,

V/T2 and W/T3 when the length of each wire does not exceed 30m.
The numeric values in parentheses refer to the sizes of wires to be used when a DC reactor is connected.

Note 2: For the control circuit, use shielded wires 0.75 mm

2

or more in diameter.

Note 3: For grounding, use a cable with a size equal to or larger than the above.
Note 4: The wire sizes specified in the above table apply to HIV wires (cupper wires shielded with an insulator

with a maximum allowable temperature of 75°C) used at an ambient temperature of 50°C or less.

Note 5: If there is a need to bring the inverter into UL compliance, use wires specified in Chapter 6.

2.2.3 Control circuit terminals

P24

PP

VIA VIB CC

PLC

S1

S2

S3

FM VIA

PLC

SOURCE

SINK

SW1

OUT NO

FM

CC

FLA FLB FLC RY

RC

F

R

RES CC

V

I

V

I

Optional connector
(RJ45)

M3 screw
(0.5N m)

Factory default settings of slide switches

SW1: SINK (Negative) side (WN, AN type)

SOURCE (Positive) side (WP type)

FM: V side
VIA: V side

Wire size

Solid wire: 0.3

∼ 1.5 (mm

2

)

Stranded wire: 0.3

∼ 1.5 (mm

2

)

(AWG 22

∼ 16)

Sheath strip length: 6 (mm)

Screwdriver: Small-sized flat-blade screwdriver

(Blade thickness: 0.4 mm or less,
blade width: 2.2 mm or less)

The control circuit terminal
board is common to all
equipment.