Operation mode parameters – Toshiba VF-S11 User Manual
Page 57
E6581160
56
7
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
E6581158
H
0273
Jumping width 2
Hz
0.1/0.01
0.0-30.0
0.0
6.10
H
0274
Jump frequency 3
Hz
0.1/0.01
0.0-HJ
0.0
H
0275
Jumping width 3
Hz
0.1/0.01
0.0-30.0
0.0
H
0287
Preset-speed
operation frequency
8
Hz
0.1/0.01
NN
-WN
0.0
H
0288
Preset-speed
operation frequency
9
Hz
0.1/0.01
NN
-WN
0.0
H
0289
Preset-speed
operation frequency
10
Hz
0.1/0.01
NN
-WN
0.0
H
0290
Preset-speed
operation frequency
11
Hz
0.1/0.01
NN
-WN
0.0
H
0291
Preset-speed
operation frequency
12
Hz
0.1/0.01
NN
-WN
0.0
H
0292
Preset-speed
operation frequency
13
Hz
0.1/0.01
NN
-WN
0.0
H
0293
Preset-speed
operation frequency
14
Hz
0.1/0.01
NN
-WN
0.0
5.14
H
0294
Preset-speed
operation frequency
15
(Fire-speed)
Hz
0.1/0.01
NN
-WN
0.0
5.14
6.11.2
• Operation mode parameters
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
E6581158
H
0300
PWM carrier
frequency
kHz
0.1/0.1
2.0 - 16.0
12.0
6.12
H
0301
Auto-restart
control selection
-
-
0: Disabled
1: At auto-restart after momentary
stop
2: ST terminal on or off
3: At auto-restart or when turning ST-
CC on or off
4: At start-up
0
6.13.1
H
0302
Regenerative
power ride-
through control
(Deceleration
stop)
-
-
0: Disabled
1: Automatic setting
2: Slowdown stop
0
6.13.2
H
0303
Retry selection
(number of times)
Times
1/1
0: Disabled
1-10
0
6.13.3
H
0304
Dynamic braking
selection
-
-
0: Disabled
1: Enabled (Resistor overload
protection enabled)
0
6.13.4
H
0305
Overvoltage limit
operation
(Slowdown stop
mode selection)
-
-
0: Enabled
1: Disabled
2: Enabled (Quick deceleration)
3: Enabled (Dynamic quick
deceleration)
2
6.13.5