Connection, 1 standard connections, 1 standard connection diagram 1 – Toshiba VF-S11 User Manual

Page 11: Vf-s11

background image

E6581160

10

2

2. Connection

2.1

Standard connections

2.1.1 Standard connection diagram 1

This diagram shows a standard wiring of the main circuit.

MCCB

*1

R/L1
S/L2
T/L3

U/T1
V/T2

W/T3

I M

FLC

FLB

FLA

RY

RC

PLC

Motor

F

R

RES

S1

S2

S3

CC

P24

OUT

NO

CC

FM

PLC

CC VIA

VIB

PP

+

+

-

-

P0

PA/+

PB

PC/-

Meter

Voltage signal: 0-10V
(Current signal: 4-20mA)

External potentiometer (1~10k

Ω)

(or input voltage signal across VIB-CC terminals: 0-10V)

Control

circuit

Operation panel

Protective function
activation output

Ry

VF-S11

Frequency

meter

(ammeter)

Power circuit

Noise
filter

DC reactor (DCL)
*2 (option)

Connector for
common serial
communications

Forward

Reverse

Reset

Preset-speed 1

Preset-speed 2

Preset-speed 3

Common

Braking resistor (option)

Standard connection diagram - SINK (Negative) (common:CC)

Low-speed
signal output

24Vdc input

7.5V-1mA
(or 4-20mA)

MCCB(2P)

R/L1

S/L2

Power supply
1 200~240V
-50/60Hz

Speed reach
signal output

I

I

SINK

SW1

SOURCE

FM

V

VIA

V

Main circuit power supply

240V class: three-phase 200-240V

-50/60Hz

500V class: three-phase 380-500V

-50/60Hz

600V class: three-phase 525-600V

-50/60Hz

*1: The T/L3 terminal is not provided

for single-phase models.

Use the R/L1 and S/L2 terminal

as input terminals.

*2: The inverter is supplied with the PO

and the PA/+ terminals shorted by

means of a shorting bar.

Before installing the DC reactor (DCL),

remove the bar.

*3: When using the OUT output terminal in

sink logic mode, short the NO and CC

terminals.

*4: If you are using a 600V model, be sure

to connect an input reactor (ACL).

*5: 600V models have no noise filter inside.

*3