Toshiba VF-S11 User Manual
Page 52
E6581160
51
7
Title
Communication
No.
Function
Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
E6581158
HOUN
0005
Meter selection
-
-
0: Output frequency
1: Output current
2: Set frequency
3: DC voltage
4: Output voltage command value
5: Input power
6: Output power
7: Torque
8: Torque current
9: Motor cumulative load factor
10: Inverter cumulative load factor
11: PBR (braking reactor) cumulative
load factor
12: Frequency setting value (after
PID)
13: VIA Input value
14: VIB Input value
15: Fixed output 1 (Output current:
100%)
16: Fixed output 2 (Output current:
50%)
17: Fixed output 3 (Other than the
output current: 100%)
18: Serial communication data
19: For adjustments (HO set value is
displayed.)
0
5.5
HO
0006
Meter adjustment
-
-
-
-
5.5
V[R
0007
Default setting
-
-
0: -
1: 50Hz default setting
2: 60Hz default setting
3: Default setting (Initialization)
4: Trip record clear
5: Cumulative operation time clear
6: Initialization of type information
7: Save user-setting parameters
8. Load user-setting parameters
9. Cumulative fan operation time
record clears
0
4.2.6
4.2.7
5.6
HT
0008
Forward/reverse
run selection
(Operation panel)
-
-
0: Forward run
1: Reverse run
2: Forward run (F/R switching
possible)
3: Reverse run (F/R switching
possible)
0
5.7
CEE
0009
Acceleration time
1
S
0.1/0.1
0.0-3200
10.0
5.1.2
FGE
0010
Deceleration time
1
S
0.1/0.1
0.0-3200
10.0
5.1.2
HJ
0011
Maximum
frequency
Hz
0.1/0.01
30.0-500.0
80.0
5.8
WN
0012
Upper limit
frequency
Hz
0.1/0.01
0.5- HJ
50.0 (WP)
60.0
(WN, AN)
5.9
NN
0013
Lower limit
frequency
Hz
0.1/0.01
0.0- WN
0.0
5.9
XN
0014
Base frequency 1
Hz
0.1/0.01
25-500.0
50.0 (WP)
60.0
(WN, AN)
5.10
XNX
0409
Base frequency
voltage 1
V
1/0.1
50-330 (240V class)
50-660 (500/600V class)
*3
5.10
6.13.6
*3 : 230 (240V class), 460 (500V class), 575V (600V class)