beautypg.com

Trane RT-PRC010-EN User Manual

Page 67

background image

67

RT-PRC010-EN

Note:
1. Important: Maximum static pressure leaving the rooftop is 4.0” H

2

O positive. The static pressure drops from the supply fan to the space cannot exceed 4.0” H

2

O.

Cfm

Total Static Pressure

Std.

6.250

6.500

6.750

7.000

7.250

7.500

Air

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

31000

1434

48.20

1459

50.30

1484

52.52

1508

54.60

1532

56.79

1557

59.10

1579

61.23

32000

1442

49.55

1464

51.55

1489

53.77

1512

55.85

1538

58.33

1559

60.35

1584

62.78

33000

1451

51.09

1473

53.11

1496

55.23

1518

57.33

1541

59.53

1565

61.85

1589

64.28

34000

1461

52.70

1482

54.63

1506

56.90

1527

59.03

1550

61.26

1570

63.29

1594

65.73

35000

1471

54.27

1491

56.22

1515

58.53

1536

60.68

1558

62.93

1578

64.99

1601

67.45

36000

1482

55.91

1503

58.03

1523

60.10

1544

62.28

1566

64.55

1589

66.93

1609

69.11

37000

1494

57.77

1514

59.79

1534

61.91

1555

64.11

1576

66.42

1597

68.68

1618

71.04

38000

1505

59.46

1527

61.78

1547

63.94

1568

66.19

1586

68.24

1608

70.69

1627

72.92

39000

1518

61.37

1540

63.74

1560

65.94

1579

68.09

1598

70.33

1617

72.50

1638

74.92

40000

1533

63.50

1552

65.66

1572

67.90

1592

70.24

1610

72.37

1629

74.58

1649

77.03

41000

1547

65.62

1566

67.82

1585

69.97

1603

72.20

1624

74.68

1642

76.94

1661

79.28

42000

1561

67.70

1580

69.96

1598

72.15

1617

74.44

1635

76.65

1654

79.10

43000

1576

69.89

1593

72.06

1613

74.46

1630

76.64

1650

79.22

44000

1591

72.20

1609

74.43

1628

76.89

1645

79.12

45000

1607

74.63

1625

76.92

1643

79.30

46000

1624

77.20

1641

79.40

Notes:
1. Shaded areas indicate non-standard BHP or RPM selections. Contact your local Trane representive for more information.
2. Supply fan performance table includes internal resistance of rooftop. For total static pressure determination, system external static must be added to appropriate component

static pressure drops, (evaporator coil, filters, optional economizer, optional heating system, optional roof curb).

3. Maximum static pressure leaving the rooftop is 4.0’’ H20 positive. The static pressure drops from the supply fan to the space cannot exceed 4.0’’ H20.
4. Maximum Cfm as follows: 105 Ton Std. — 44,000 Cfm, 105 Hi-Cap., 115, 130 Tons — 46,000 Cfm
5. Minimum motor horsepower is 30 hp.
6. See RT-EB-104 for further details.

Table PD-43 — Supply Fan Performance WITH INLET GUIDE VANES — 105,115,130 Tons (Cont.)

Figure PD-12 — Supply Fan Performance WITH INLET GUIDE VANES — 105,115,130 Tons

(105,115,130 Tons)

Performance
Data

0

10000

20000

30000

40000

50000

60000

0

1

2

3

4

5

6

7

8

9

4

0

%

W

O

C

F

M

5

0

%

W

O

C

F

M

6

0

%

W

O

C

F

M

90%

WO

CFM

80

%

W

O

CF

M

7

0

%

W

O

C

F

M

10

0

H

P

7

5

H

P

60

H

P

5

0

H

P

40

H

P

3

0

H

P

2

5

H

P

20

H

P

1600 RPM

1500 RPM

1400 RP

M

1300 RPM

1200 RPM

1100 RPM

1000 RPM

900 RPM

CFM

S

tat

ic

P

re

s

ur

e,

I

n

c

h

e

s

w

.c

.