RT-PRC010-EN

Figure PD-5 — Supply Fan Performance With VARIABLE FREQUENCY DRIVE or WITHOUT INLET VANES — 40, 50 and 55 Tons

Note:
1. Important: Maximum static pressure leaving the rooftop is 4.0” H

2

O positive. The static pressure drops from the supply fan to the space cannot exceed 4.0” H

2

O.

Performance
Data

(40, 50, 55 Tons)

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

5.5

6.0

6.5

7.0

7.5

8.0

0

2000

4000

6000

8000 10000 12000 14000 16000 18000 20000 22000 24000 26000 28000 30000

CFM

STATIC PRESSURE, Inches w.c.

40 HP

7.5 HP

10 HP

15 HP

20 HP

25 HP

30 HP

1200 RPM

600 RPM

700 RPM

800 RPM

900 RPM

1000 RPM

1100 RPM

500 RPM

5 HP

40% wocfm

50%

60%

70%

SQHFC40, C50, C55
Dual 20 X 20 Fans
Entrance Losses
- w ithout Inlet Guide Vanes
- w ithout Evap Coil
- w ithout Filters
- w ithout Return Air Dampers
- w ithout Exhaust
Fan Curve Limits
- Minimum Motor HP = 7.5
- Maximum Motor HP
C40 = 25 HP
C50 & C55 = 30 HP
- Maximum RPM
7.5 - 15 HP = 1141
20 - 30 HP = 1170
- Maximum CFM
C40 = 18,000
C50 = 22,500
C55 = 24,000
- Maximum Static Pressure
Leaving the Unit = 4.0" w .c.

90%

80%