General data – Trane RT-PRC010-EN User Manual

Page 27

background image

27

RT-PRC010-EN

Table GD-3 — General Data — 90-130 Tons Continued

90 Ton

105 Ton

115 Ton

130 Ton

Filters

Panel Filters

Number/Size (Inches)

25-24x24x2

25-24x24x2

25-24x24x2

25-24x24x2

Face Area (Ft

2

)

100.0

100.0

100.0

100.0

Bag Filters

3-12x24x19

3-12x24x19

3-12x24x19

3-12x24x19

Number/Size (Inches)

15-24x24x19

15-24x24x19

15-24x24x19

15-24x24x19

Cartridge Filters

3-12x24x12

3-12x24x12

3-12x24x12

3-12x24x12

15-24x24x12

15-24x24x12

15-24x24x12

15-24x24x12

Prefilters (For Bag & Cartridge)

3-20x24x2

3-20x24x2

3-20x24x2

3-20x24x2

15-24x24x2 15-24x24x2 15-24x24x2 15-24x24x2

Face Area (Ft

2

)

66.0

66.0

66.0

66.0

Standard Unit Min. Outside Air Temperature For Mechanical Cooling

Without Hot Gas Bypass

45 F

45 F

45 F

45 F

With Hot Gas Bypass

45 F

45 F

45 F

45 F

Notes:
1. For cfm values outside these ranges, refer to RT-EB-104.
2

Refer to Table PD-30 for availability of electric heat kw ranges by voltage.

3. 90-130 Ton models are dual circuit.
4. Max cfm for 105 Ton std is 44,000.
5

The firing rate of the unit can vary from 33% of the Heater Mbh up to the nameplate rating of the unit.

6. The firing rate of the unit can vary from pilot rate of 125,000 Btuh up to the nameplate rating of the unit.

Table GD-4 — ARI Performance Data

1

ARI Performance Data

1

Capacity

Tons

Model

3

(MBh)

EER

IPLV

2

SAHFC2040A**A**A*****

220

9.5

12.8

SXHFC2040A**A**A*****

220

9.5

12.8

20

SFHFC204LA**A**A*****

220

9.4

12.7

SEHFC204*A**A**A*****

220

9.4

12.7

SLHFC204LA**A**A*****

220

9.4

12.6

SSHFC204LA**A**A*****

220

9.4

12.7

Notes:
1. This information is rated and tested in accordance with ARI Standard 360-93

for large unitary equipment up to 25 tons. These Trane products can be
found in the current ARI Directory.

2. IPLV — Integrated Part Load Value
3. This information applies to units whose design sequence (Digit 10) is “A” or

later.

Table GD-5 — ARI Correction Multipliers

Model

Multipliers (%)

Option Description

Digit

Designator

Capacity

EER

IPLV

2

High Heat — Gas

9

H,J,P

100

100

100

High Heat — Steam

9

H

100

99

98

High Heat — Hot Water

9

H

100

99

99

Wire Mesh Filter

13

B

100

101

101

95% Bag filter

13

D

99

95

91

95% Cartridge Filter

13

E

99

95

92

100% Economizer

16

D

100

99

98

High Capacity Coil

21

G

114

109

107

High Efficiency Motor

21

L

100

101

101

Inlet Guide Vanes

17

3

100

99

99

VFD (60 Hz)

17

6-9

99

98

98

Table GD-6 — Economizer Outdoor Air Damper Leakage (Of Rated Airflow)

P Across Dampers (In. WC)

0.5 (In.)

1.0 (In.)

Standard “Low Leak”

1.5 %

2.5 %

Optional “Ultra Low Leak”

0.5 %

1.0 %

Note:
1. Above data based on tests completed in accordance with AMCA Standard 575 at AMCA

Laboratories.

General Data