beautypg.com

Trane RT-PRC010-EN User Manual

Page 55

background image

55

RT-PRC010-EN

Note:
1. Important: Maximum static pressure leaving the rooftop is 4.0” H

2

O positive. The static pressure drops from the supply fan to the space cannot exceed 4.0” H

2

O.

Figure PD-6 — Supply Fan Performance WITH INLET VANES — 40, 50 and 55 Ton

(40, 50, 55 Tons)

Performance
Data

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

5.5

6.0

6.5

7.0

7.5

8.0

0

2000

4000

6000

8000 10000 12000 14000 16000 18000 20000 22000 24000 26000 28000 30000

CFM

STATI

C

PRESSURE,

I

n

c

h

e

s

w.

c

.

40%

w

o

cfm

50%

60%

70%

1200 RPM

500 RPM

600 RPM

700 RPM

800 RPM

900 RPM

1000 RPM

1100 RPM

5 HP

7.5 HP

10 HP

15 HP

20 HP

25 HP

30 HP

40 HP

S_HFC40, C50, C55
Dual 20 X 20 Fans
Entrance Losses
- w ith Inlet Guide Vanes
- w ithout Evap Coil
- w ithout Filters
- w ithout Return Air Dampers
- w ithout Exhaust
Fan Curve Limits
- Minimum Motor HP = 7.5
- Maximum Motor HP
C40 = 25 HP
C50 & C55 = 30 HP
- Maximum RPM
7.5 - 15 HP = 1141
20 - 30 HP = 1170
- Maximum CFM
C40 = 18,000
C50 = 22,500
C55 = 24,000
- Maximum Static Pressure
Leaving the Unit = 4.0" w .c.

90%

80%