Table PD-31— Hot Water Heating Capacities (Q/ITD)

1

20, 25, 30 Nominal Tons

Hot Water

Water

Unit Standard Air Volume (Cfm)

Module

Gpm

PD (Ft)

4000

6000

8000

10000

12000

14000

Low

10

0.54

1.65

1.99

2.21

2.37

2.48

2.56

High

20

0.91

2.23

2.78

3.16

3.44

3.67

3.85

Low

20

0.91

1.88

2.35

2.69

2.94

3.12

3.27

High

30

1.49

2.36

3.00

3.46

3.81

4.09

4.31

Low

30

1.49

1.97

2.51

2.90

3.19

3.42

3.60

High

40

2.25

2.43

3.12

3.63

4.02

4.34

4.60

Low

40

2.25

2.02

2.60

3.02

3.34

3.60

3.79

High

50

3.2

2.48

3.20

3.74

4.17

4.51

4.80

Low

60

4.31

2.08

2.69

3.16

3.51

3.79

4.02

High

70

5.65

2.54

3.30

3.88

4.35

4.73

5.04

40, 50, 55 Nominal Tons

Hot Water

Water

Unit Standard Air Volume (Cfm)

Module

Gpm

PD (Ft)

8000

11000

14000

17000

20000

23000

Low

20

0.70

3.00

3.44

3.75

3.98

4.14

4.29

High

30

1.05

3.85

4.46

4.91

5.26

5.54

5.76

Low

40

1.51

3.40

4.00

4.43

4.76

5.02

5.21

High

50

2.10

4.20

4.95

5.52

5.97

6.34

6.64

Low

60

2.78

3.56

4.23

4.73

5.11

5.40

5.63

High

75

4.04

4.39

5.24

5.89

6.41

6.85

7.21

Low

80

4.50

3.65

4.36

4.89

5.31

5.63

5.88

High

90

5.54

4.46

5.34

6.03

6.58

7.04

7.42

Low

100

6.66

3.71

4.44

5.00

5.43

5.77

6.04

High

125

9.99

4.56

5.50

6.23

6.83

7.33

7.75

60, 70, 75 Nominal Tons

Hot Water

Water

Unit Standard Air Volume (Cfm)

Module

Gpm

PD (Ft)

12000

16000

20000

24000

28000

31500

Low

25

0.98

4.28

4.82

5.20

5.48

5.69

5.83

High

30

1.22

5.24

5.91

6.40

6.77

7.06

7.27

Low

50

2.48

4.90

5.63

6.18

6.60

6.92

7.15

High

60

3.33

6.01

6.94

7.66

8.22

8.69

9.03

Low

75

4.83

5.14

5.97

6.60

7.09

7.46

7.73

High

90

6.65

6.32

7.38

8.20

8.87

9.42

9.83

Low

100

8.0

5.28

6.16

6.84

7.36

7.78

8.07

High

120

11.15

6.49

7.62

8.51

9.23

9.84

10.30

Low

125

11.99

5.37

6.29

6.99

7.54

7.98

8.29

High

150

16.8

6.60

7.77

8.71

9.47

10.11

10.60

90, 105, 115, 130 Nominal Tons

Hot Water

Water

Unit Standard Air Volume (Cfm)

Module

Gpm

PD (Ft)

27000

30000

33000

36000

39000

42000

Low

30

0.77

6.68

6.87

7.04

7.18

7.30

7.41

High

40

1.02

8.51

8.80

9.04

9.26

9.45

9.62

Low

60

1.69

8.07

8.38

8.64

8.87

9.07

9.25

High

80

2.6

10.21

10.64

11.03

11.38

11.69

11.98

Low

100

3.71

8.82

9.19

9.52

9.80

10.05

10.26

High

120

5.07

10.95

11.46

11.92

12.33

12.71

13.05

Low

140

6.59

9.19

9.60

9.96

10.27

10.55

10.79

High

160

8.37

11.37

11.93

12.43

12.88

13.30

13.67

Low

175

9.8

9.39

9.82

10.20

10.53

10.82

11.07

High

200

12.52

11.64

12.23

12.76

13.24

13.68

14.08

Note:
1. Capacities expressed as MBh per initial temperature difference (ITD) between the entering air temperature to

the hot water coil and the entering water temperature. Ethylene glycol or other capacities can be determined
from the Trane heating coil computer program. Capacity and pressure drop of ethylene glycol varies greatly
with temperature and concentration.