beautypg.com

Caution, Refrigerant piping connection, For reference – Toshiba RAV-SM1100UT-E User Manual

Page 9: Optional installation parts (local procure), Knockout of pipe cover

background image

6

Refrigerant Piping Connection

CAUTION

TAKE NOTICE THESE IMPORTANT
4 POINTS BELOW FOR PIPING WORK

1. Keep dust and moisture away from inside the

connecting pipes.

2. Tightly connect the connection between pipes

and the unit.

3. Evacuate the air in the connecting pipes using

VACUUM PUMP.

4. Check gas leak at connected points.

Liquid side

Outer diameter Thickness

Ø9.5

0.8

Gas side

Outer diameter Thickness

Ø15.9

1.0

For Reference

If a heating operation would be continuously performed
for a long time under the condition that the outdoor
temperature is 0°C or lower, draining of defrosted water
may be difficult due to freezing of the bottom plate,
resulting in a trouble of the cabinet or fan.

It is recommended to procure an anti-freeze heater
locally for a safety installation of the air conditioner.

For details, contact the dealer.

Optional Installation Parts (Local Procure)

Knockout procedure

• The indoor/outdoor connecting pipes can be con-

nected to 4 directions.

Take off the knockout part of the pipe cover in which
pipes or wires pass through the base plate.

• As shown in the figure, do not remove the pipe cover

from the cabinet so that the knockout hole can be
easily punched. To knock out, it is easily taken off by
hands by punching a position at the lower side of 3
connected parts with screwdriver along the guide
line.

• After marking the knockout hole, remove the burr and

mount the attached protective bush and guard
material for pass-through part in order to protect
pipes and wires.

After connecting the pipes, be sure to mount the pipe
cover. The pipe cover is easily mounted by cutting off
the slit at the lower part of the pipe cover.

Front direction

Rear direction

Pipe cover

Side direction

Down direction

A

B

C

Parts name

Refrigerant piping
Liquid side : Ø9.5 mm
Gas side

: Ø15.9 mm

Pipe insulating material
(polyethylene foam, 6 mm thick)

Putty, PVC tapes

Q’ty

Each one

1

Each one

Knockout of Pipe Cover