Toshiba RAV-SM1100UT-E User Manual
Page 78
75
Setup of the Ad
dress No.
T
o
connect the indoor unit to the central remote controller using the adapter
, it is necessar
y to set up the netw
or
k address No
.
•
It is required to ag
ree the netw
or
k address No
. with the centr
al remote controller system No
.
•
The netw
or
k address No
. is set to 1 at the shipment from the f
actor
y.
The f
ollowing tw
o methods are used f
or setup
.
1.
Setup fr
om the remote contr
oller at the indoor unit side
•
This method is a
v
ailab
le only when [7] of the setup s
witch SW01 on the adapter P
.C
. board is OFF
.
ocedure> Set up the ad
dress No.
while the air conditioner stops.
1
Push
and
b
uttons f
or 4 seconds or more
.
In case of the g
roup control, the unit No
.
ALL
is displa
y
ed, and then all the indoor units in the group control are selected.
(Fig. 1)
In this time
, the f
ans of all the selected indoor units star
t and the s
wing oper
ation also star
ts in the models with flaps
.
(K
eep the displa
y status of
ALL
without pushing
UNIT
b
utton.)
In case of individual
remote controller
with no group control, the system address and the indoor unit address are displa
y
ed.
(Fig. 1)
Setup data
0001
0002
0003
•
•
•
0064
0099
Netw
ork address No.
1
2
3
•
•
•
64
No setting (Shipment from the f
actor
y.
)
UNIT
UN
IT
No
.
CODE No.
SET DATA
R.C.
No.
SET
CL
1
5
2
3
4
2
Using
/
b
uttons,
specify the item code
03
.
3
Using
b
uttons,
select the setup data.
The f
ollo
wing tab
le sho
ws the setup data.
(T
a
b
le 1)
4
Push
SET
b
utton.
(When the displa
y goes on,
the setup data is accepted.)
T
o
change the setup item, retur
n to the step
2
.
5
Push
b
utton.
The status returns to the normal stop status.
(T
ab
le 1)
2.
Setup b
y
the s
witch on the adapter P
.C.
boar
d
When the remote controller is not f
ound, or when y
ou do not w
ant to change the setup of networ
k address No
. on the remote
controller
, set up the address No
. b
y
using the setup s
witch SW01 (Netw
or
k address No
. setup s
witch) on the adapter P
.C
.
board.
ocedure>
1
T
urn off the po
wer suppl
y.
2
Set [7] of the address No.
setup s
witc
h
SW01 to ON side
.
Accordingly
, the setup of the address No
. from
the remote controller is in
v
alidated.
(Fig.
2)
3
The netw
ork ad
dress No.
is set up b
y
com-
bining ON/OFF of the ad
dress No.
setup
s
witc
h,
fr
om SW01 [6] to [1].
F
or the relation betw
een ON/OFF combination
and the address No
., see (T
a
b
le 2).
A case when the address No
. is set to 16 is
sho
wn in (Fig.
3).
When the networ
k address No
. has been changed, tur
n on the po
wer of the centr
al remote controller
again or reset the
centr
al remote controller from the reset hole on the control panel of the centr
al remote controller
.
SW01
ON side
OFF side
(Numeral side)
1234567
Address No. setup on the remote controller is invalid.
Address No. setup
Setup example (Address No. 16)
ON side
OFF side
(Numeral side)
1234567
(Fig. 2)
(Fig. 3)
Ad
dress No.
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Ad
dress No.
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
Ad
dress No.
setup tab
le (SW01)
(T
ab
le 2)
:
ON side
,
:
OFF side
Requirement in Ser
vice
Time
When using this pr
oduct as the ser
vice par
t f
or c
hang
e of the adapter P
.C.
boar
d,
be sure to set the setup s
witc
h SW01
(Netw
ork ad
dress No.
setup s
witc
h) on the adapter P
.C.
boar
d so that it is same as one bef
ore c
hange
.