Before test run

• Before turning on the power supply, carry out the following procedure.

1) Using 500V-megger, check 1M

Ω or more exists between the terminal block 1 to 3 and the earth.

If 1M

Ω or less is detected, do not run the unit. Do not apply to the remote controller circuit.

2) Check the valve of the outdoor unit being opened fully.

• To protect the compressor at activation time, leave power-ON for 12 hours or more be for operating.

How to execute a test run

Using the remote controller, operate the unit as usual.
For the procedure of the operation, refer to the attached Owner’s Manual.
A forced test run can be executed in the following procedure if the operation stops by thermo.-OFF.

In order to prevent a serial operation, the forced test run is released after 60 minutes have passed and returns to the
usual operation.

CAUTION

When the remote controller is used for the first time, it accepts an operation approx. 5 minutes after the power
supply has been turned on.
It is not a trouble, but is because the setup of the remote controller is being checked.

For the second power-ON time and after, approx. 1 munute is required to start the operation by the remote
controller.

NOTE

Do not use the forced test run for cases other
than the test run because it applies an
excessive load to the devices.

In case of wired remote controller

UNIT

SET

CL

1, 5

3

2, 4

Procedure

1

2

3

4

5

Description

Keep

button pushed for 4 seconds or more. [TEST] is

displayed on the display part and the selection of mode in the test
mode is permitted.

Push

button.

Using

button, select the operation mode, [COOL] or [HEAT].

• Do not run the air conditioner in a mode other than [COOL] or

[HEAT].

• The temperature controlling function does not work during test run.

• The detection of error is performed as usual.

After the test run, push

button to stop a test run.

(Display part is same as procedure

1

.

Push

check button to cancel (release from) the test run mode.

([TEST] disappears on the display and the status returns to a
normal.)