MANOMETER

GAS PRESSURE

TEST AT GAS

VALVE

GAS PRESSURE TEST

AT HEATER

MANUAL

SHUTOFF

VALVE

GAS PRESSURE

TEST UPSTREAM

Model

No.

1”

1-1/4”

1-1/2”

2”

2-1/2”

3”

4”

N

P

N

P

N

P

N

P

N

P

N

P

N

P

926/962

15

20

45

45

110 150

360

400

1083/1125

10

15

35

35

80

120

300

300

1178/1223

25

25

60

85

220

200

1287/1336

25

20

55

75

180

170 325 560

1414/1468

20

15

45

65

150

165 300 500

1571/1631

15

15

35

50

20

125 250 400

1758/1826

15

10

30

40

100

100 225 340

2100

10

10

25

30

80

75

175 260

2500

15

20

55

55

135 160 400 600

3001

10

15

35

40

85

120 250 500

3500

10

30

30

45

80

200 400 600

4001

5

20

25

35

65

160 300 400

Natural Gas, 1000 BTU/FT

3

.60 Specific Gravity @ 0.5 in. WC Pressure Drop

Propane Gas, 2500 BTU/FT

3

1.53 Specific Gravity @ 0.6 in. WC Pressure Drop

Table B: Maximum Equivalent Pipe Length

Fig. 6: Gas Pressure Test Points

Venting of Diaphragm Gas

Components

Heaters with gas train components that have

diaphragms in their construction are supplied with a

bleed line connection that must be connected to the

outside atmosphere as required by the National Fuel

Bleed Line

Connection

Fig. 7: Bleed Line Connection

Gas Code. Under NO circumstances shall bleed lines

terminate in the gas utilization equipment flue or

exhaust system.