Low Water Cutoff

Automatically shuts down burner whenever water

level drops below probe. A 3 to 5 second time delay

prevents premature lockout due to temporary condi-

tions such as power failure or air pockets. Standard on

Cal Code heaters.

High & Low Gas Pressure Switches

Pressure switches sense either high or low gas pres-

sure and automatically shut down burners if abnormal

pressures exist. Standard on Models 3001-4001.

Electrical Wiring

Electronic Ignition

The intermittent ignition device conserves energy by

automatically extinguishing the pilot when desired

temperature is reached. When additional heat is need-

ed, the pilot re-ignites electrically, eliminating the fuel

costs of maintaining a constant pilot. To ensure safe

operation, the gas valve cannot open until the pilot

relights and is confirmed.

Heater must be electrically grounded and bonded in

accordance with local codes, or, in the absence of

local codes, with the latest edition of the National

Electrical Code, ANSI/NFPA 70.

Fig. 25: Low Water Cutoff

Fig. 26: High/Low Gas Pressure Switch

Model

Without Lockout

With Lockout

N

P

N

P

926–1826

Standard

N/A

Optional Standard

2100–4001

N/A

N/A

Standard Standard

CAUTION: Label all wires prior to disconnection

when servicing controls. Wiring errors can cause

improper and dangerous operation. Verify proper

operation after servicing.

DANGER - SHOCK HAZARD - Make sure

electrical power to the heater is disconnected to

avoid potential serious injury or damage to

components.

NOTE: If it is necessary to replace any of the

original wiring, it must be replaced with 105° C wire

or its equivalent.

Table E: Lockout Availability

Fig. 27: Ignition Module