beautypg.com

Clearances, Combustion ai, Indoor units only) – Raypak RAYTHERM P-926 User Manual

Page 6: Combustion air (indoor units only)

background image

6

Clearances

All Heaters

For clearances from combustible surfaces, see Table

A below. We require a minimal vertical clearance of

three feet between the upper surface of the flue outlet

to a noncombustible material.

For servicing, provide at least 24" in front of the heater

on Models 926-1826 & 48" in front of the heater on

Models 2100-4001 for burner tray removal, and at

least 18" on the right side of the heater to inspect and

delime the heat exchanger.

Outdoor Heaters (Models 926-1758)

These heaters are design certified for outdoor installa-

tion, when equipped with the approved top designated

for outdoor use. Heaters must not be installed under

an overhang of less than three (3) feet from the top of

the heater. Three (3) sides must be open in the area

under the overhang. Roof water drainage must be

diverted away from heaters installed under overhangs

with the use of gutters.

The point from where the flue products exit the heater

must be a minimum of four (4) feet below, four (4) feet

horizontally from or one (1) foot above any door, win-

dow or gravity inlet to a building. The top surface of the

heater shall be at least three (3) feet above any forced

air inlet, or intake ducts located within ten (10 ) feet

horizontally.

High Wind Conditions

(Outdoor Units Only)

In areas where high winds are frequent, it may be nec-

essary to locate the heater a minimum of 3' from high

vertical walls, or install a wind break so the heater is

not in direct wind current.

Indoor Heaters

The design is also certified for indoor installation when

equipped with approved drafthood. Locate heater as

close as practical to a chimney or gas vent.

Combustion Air

(Indoor Units Only)

The heater must have both combustion and ventilation

air. Openings must not be obstructed. Minimum

requirements are as follows:

1. Free combustion air 1 sq. in. per 1000 BTU input

within 12" of the floor.

Indoor Heaters

Outdoor Heaters

(926–1758)

Heater

Side

Clearance

(Inches)

Heater

Side

Clearance

(Inches)

Top

24

Top

24

Back

24

Back

24

Right Side

24

Right Side

24

Left Side

24

Left Side

24

Vent*

6

Table A: Minimum Clearances from Combustible

Construction

*Vent includes factory supplied drafthood and does not include field

supplied vent systems above the drafthood. On Models 2100-4001

drafthood is built into heater.

For servicing provide a front clearance as shown below:

Model 926/962-758/1826 - 24"

Model 2100-4001 - 48"

WARNING: The heater shall not be located in an

area where water sprinklers, or other devices, may

cause water to spray through the cabinet louvers

and into the heater. This could cause heavy internal

rusting or damage some electrical components, and

this would void the warranty.

Fig. 2: Minimum Distance from Openings

CAUTION: Combustion air must not be

contaminated by corrosive chemical fumes which

can damage the heater and void the warranty.

This manual is related to the following products: