Raypak recommends the installation of an air bleed

vent at a suitable location (usually the highest point in

the plumbing) to remove air from the piping system.

These units should be available at your local whole-

sale supplier. Raypak does not provide this item.

Models 1287 through 4001 are equipped with an

external pump and bypass arrangement that blends

outlet water with the inlet to increase the inlet water

temperature, thereby reducing the likelihood of con-

densation forming on the heat exchanger. The pump

also serves to circulate water through the heater from

the main system piping.

To complete the installation of the pool heater, the pool

thermostat needs to be installed in the main return

water line. This will ensure that the heater will be ener-

gized at the right time. If the main water line is too far

away from the heater and the capillary bulb will not

reach it, locate the pool thermostat adjacent to the

main line and run wires back to the heater. Follow the

instructions listed below to install the poolstat.

Mounting the Poolstat Control

with Front-Mounted Loop

Using Mounting Slots

For heater models:

1287, 1336, 1414, 1468, 1571, 1631, 1758, 1826,

2100, 2500, 3001, 3500, 4001.

1. Remove the poolstat control cover by removing

the two cover screws at the top. See Fig. 13 & 14.

CAUTION: Power to the heater should be

interlocked with the main system pump to make sure

the heater does not fire without the main system

pump in operation. Improper flow control can

damage the heater. Uncontrolled flow (too high) or

restricted flow (too low) can seriously affect heater

operation. Follow these instructions to make sure

your heater is properly installed.

NOTE: For more detail on piping, refer to the

diagrams on pages 15, 16 & 17.

Inlet/Outlet
Header

2-1/2" Inlet

2-1/2" Outlet

1-1/2" Slip Ball Valve

Pump

Fig. 11: Companion Flange Connections

(Models 1287/1336–1758/1826)

2" Slip
Ball Valve

3" Outlet

3" Inlet

2 H.P. Pump

Inlet/Outlet
Header

Fig. 12: Companion Flange Connections

(Models 2100–4001)

Model No. Connection

Size

Minimum

gpm

Maximum

gpm

926–1223

2” FPT

60

120

1287–1826 2-1/2” FPT

Refer to Table D

2100–4001

3” FPT

Table C: Water Connections

Model No. Loop* Flow Rates

(gpm)

Heater Flow

Rates (gpm)

1287/1336

30–50

85

1414/1468

35–55

85

1571/1631

40–65

85

1758/1826

45–70

85

2100

50–80

180

2500

60–95

180

3001

75–115

180

3500

90–135

180

4001

100–150

180

Table D: Flow Rates

*Loop is secondary piping to heater from main system.