Water Pressure Switch

On Models 926-1223 built with a Unitherm Governor

(UG), a water pressure switch is provided in the heater

to shut down the gas valves in the event the water sup-

ply to the heater is interrupted. It is very important to

verify that the switch electrically opens and shuts off

the gas valve when water flow to the heater is inter-

rupted.

Otherwise, rapid and severe damage to the heater will

likely occur. (The water pressure switch should be

checked and adjusted for proper operation by a quali-

fied service person at the time of installation and

periodically checked thereafter. Refer to pressure

switch servicing instructions in this manual).

Automatic Chlorinators and

Chemical Feeders

All chemicals must be introduced and completely dilut-

ed into the pool or spa water before being circulated

through the heater. Do not place chlorine tablets or

bromine sticks in the skimmer. High chemical concen-

trations will result when the pump is not running (eg,

overnight).

Chlorinators must feed downstream of the heater and

have an anti-siphoning device to prevent chemical

backup into the heater when the pump is shut off.

WARNING: Operation of the heater without water

circulation will cause rapid and severe damage to

the heater.

NOTE: High chemical concentrates from feeders

and chlorinators that are out of adjustment will cause

very rapid corrosion to the heat exchanger in the

heater. Such damage is not covered under the

warranty.

Unitherm Governor Operation

The patented Unitherm Governor (UG) is a thermosta-

tic mixing valve specifically designed to maintain

constant heater internal temperature between 105°

and 115°F despite continually changing flow rates from

the filter and changing pool temperatures. This narrow

range is needed to prevent damaging condensation on

the burners which will occur if the heater runs for any

length of time below 105°F. It is also needed to inhibit

scale formation in the tubes by maintaining tempera-

tures well below accelerated scaling temperatures.

The Unitherm Governor is an available option on mod-

els 926 through 1223. Where installed, it is built into

the inlet/outlet header. The larger sizes, models 1287

through 4001, do not have a UG option. Instead, they

have an externally mounted bypass pump that is

designed to maintain the water entering the heater at

the proper temperature to prevent condensation and

scale. Thermometers are provided on the inlet and

outlet to the heater.

Companion Flange

Connections

(Models 926-1223)

DO NOT use petroleum base assembly fluids (such as

Petroleum Jelly or Lubricating Oil). If assembly lube is

required use a silicone base such as Armoral etc.

The inlet/outlet header flange accepts a 2" copper tube

as a slip connection directly into the header. The

flange is also threaded for a 2" NPT copper male

adapter.

Fig. 10: Companion Flange Connections