beautypg.com

Flow rates, Maximum and minimum flow rates, Pass heat exchanger 1-pass heat exchanger – Raypak 1334001 User Manual

Page 22

background image

22

R

D

H

R

D

H

L

E

D

O

M

SIZE

GPM

T

P FT GPM

T

P FT

CONN

GPM

T

P FT GPM

T

P FT CONN

0133*

22

10

14.7

10

22

3.3

1-1/4"

0182/0181

45

7

9.2

20

15

1.8

1-1/2"

0260/0261

45

10

9.4

20

22

1.9

1-1/2"

0330/0331

45

12

9.6

20

28

1.9

1-1/2"

0400/0401

45

15

9.8

20

33

2.0

1-1/2"

0514

90

9

9

40

21

1.8

2"

0624

90

12

9.5

40

26

1.9

2"

0724

90

13

10

40

30

2.0

2"

0824

90

15

10.5

40

34

2.1

2"

0926

90

17

11

40

38

2.2

2 1/2"

200

8

9.7

90

17

2.1

3"

0962

90

18

11

40

39

2.2

2 1/2"

200

8

9.7

90

18

2.1

3"

1083

90

20

12

44

40

2.9

2 1/2"

200

9

10.3

90

20

2.3

3"

1125

90

20

12

46

40

3.1

2 1/2"

200

9

10.3

90

20

2.3

3"

1178

90

21

12.5

48

40

3.6

2 1/2"

200

10

11

90

21

2.4

3"

1223

90

22

12.5

50

40

3.9

2 1/2"

200

10

11

90

22

2.4

3"

1287

90

23

13.2

53

40

4.5

2 1/2"

200

11

11.7

90

23

2.5

3"

1336

90

24

13.2

55

40

4.9

2 1/2"

200

11

11.7

90

24

2.5

3"

1414

90

26

14

58

40

5.8

2 1/2"

200

12

12.2

90

26

2.7

3"

1468

90

27

14

60

40

6.2

2 1/2"

200

12

12.2

90

27

2.7

3"

1571

90

29

14.5

64

40

7.3

2 1/2"

200

13

13

90

29

2.8

3"

1631

90

30

14.5

67

40

8.1

2 1/2"

200

13

13

90

30

2.8

3"

1758

90

32

15.4

72

40

9.7

2 1/2"

200

14

14.7

90

32

3

3"

1826

90

33

15.4

75

40

10.6

2 1/2"

200

15

14.7

90

33

3

3"

2100

200

17

14.8

90

38

3.2

3"

400

9

18

180

19

4

4"

2500

200

20

15.8

102

40

4.3

3"

400

10

18.8

180

23

4.1

4"

3001

200

25

16.7

123

40

6.5

3"

400

12

19.5

180

27

4.3

4"

3500

200

29

17.5

144

40

9.3

3"

400

14

20.5

180

32

4.5

4"

4001

200

33

18.7

164

40

12.8

3"

400

16

21.5

180

36

4.7

4"

MAXIMUM AND MINIMUM FLOW RATES

N

I

M

N

I

M

X

A

M

MAX

2-PASS HEAT EXCHANGER

1-PASS HEAT EXCHANGER

GPM Flow rates limited by maximum acceptable velocity through heat exchanger tubes. May be increased by 10% for closed heating sys-
tems.
* 4 Pass Heat Exchanger
BOLD TYPE indicates Low NOx models.

Table H: Maximum and Minimum Flow Rates

Flow Rates