P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace

19

INSTALLATION

Diagram 3

Horizontal Venting with Two (2) 90

o

Elbows

Horizontal Venting with Two (2) 90

o

Elbows

Horizontal Venting with Three (3) 90

o

Elbows

Horizontal Venting with Three (3) 90

o

Elbows

Diagram 5

Diagram 4

Diagram 6

Option

V

H

+

H1

A)

1' (305mm) Minimum

2' (610mm) Maximum

B)

2' (610mm) Minimum

5' (1.5m) Maximum

C)

3' (914mm) Minimum

8' (2.4m) Maximum

D)

4' (1.22m) Minimum

11' (3.35m) Maximum

E)

5' (1.5m) Minimum

14' (4.27m) Maximum

F)

6' (1.86m) Minimum

15' (4.5m) Maximum

With the above options, maximum total pipe length if 37 feet
with minimum of 6 feet total vertical and maximum 15 feet total
horizontal.
Please note minimum 1 foot between 90

o

elbows is required.

Option

V

H

H + H1 + H2

A)

2' (610mm) Min. 1' (305mm) Max. 3'(914mm) Max.

B)

3' (914mm) Min. 3' (914mm) Max. 6' (1.86m) Max.

C)

4' (1.22mm) Min. 5' (1.5m) Max.

9' (2.7m) Max.

D)

5' (1.5m) Min.

7' (2.13m) Max. 12' (3.6m) Max.

With the above options, maximum total pipe length if 37 feet with minimum
of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90

o

elbows is required.

Option

V

H

H + H1

A)

1' (305mm) Min. 1' (305mm) Max. 3'(914mm) Max.

B)

2' (610mm) Min. 3' (0.91m) Max. 6' (1.86m) Max.

C)

3' (914mm) Min. 5' (1.5m) Max.

9' (2.7m) Max.

D)

5' (1.5m) Min.

8' (2.4m) Max.

12' (3.6m) Max.

With the above options, maximum total pipe length if 37 feet with minimum
of 5 feet total vertical and maximum 12 feet total horizontal.
Please note minimum 1 foot between 90

o

elbows is required.

Option

V

+

V1

H

+

H1

A)

2' (610mm) Minimum

3' (914mm) Maximum

B)

3' (914mm) Minimum

6' (1.86m) Maximum

C)

4' (1.22m) Minimum

9' (2.7m) Maximum

D)

5' (1.5m) Minimum

12' (3.6m) Maximum

With the above options, maximum total pipe length if 37 feet
with minimum of 5 feet total vertical and maximum 12 feet total
horizontal.
Please note minimum 1 foot between 90

o

elbows is required.